Submittal Sheet

● at 575/600 V rated value
0hp
Contactor
Number of NO contacts for main contacts 3
Operating voltage for main current circuit at AC at 60
Hz maximum
600V
Operating current at AC at 600 V rated value 27A
Mechanical service life (switching cycles) of the main
contacts typical
10000000
Auxiliary contact
Number of NC contacts at contactor for auxiliary
contacts
0
Number of NO contacts at contactor for auxiliary
contacts
1
Number of total auxiliary contacts maximum 8
Contact rating of auxiliary contacts of contactor
according to UL
10A@600VAC (A600), 5A@600VDC (P600)
Coil
Type of voltage of the control supply voltage AC
Control supply voltage
● at DC rated value
0...0V
● at AC at 60 Hz rated value
110...240V
● at AC at 50 Hz rated value
0...0V
Holding power at AC minimum 8.6W
Apparent pick-up power of magnet coil at AC 218V·A
Apparent holding power of magnet coil at AC 25V·A
Operating range factor control supply voltage rated
value of magnet coil
0.85...1.1
Percental drop-out voltage of magnet coil related to
the input voltage
50%
Switch-on delay time 19...29ms
Off-delay time 10...24ms
Overload relay
Product function
● Overload protection
Yes
● Phase failure detection
Yes
● Phase unbalance
Yes
● Ground fault detection
Yes
● Test function
Yes
● External reset
Yes
Reset function Manual, automatic and remote
Trip class Class 5 / 10 / 20 (factory set) / 30
US2:14DUE32BA Subject to change without notice
Page 2/
6
10/23/2017 © Copyright Siemens