Cut Sheet
010816
(800) 888-5538 sales@functionaldevices.com www.functionaldevices.com
CURRENT
SENSORS
RELAY & AC CURRENT SWITCH COMBOS
10-30 Vac/dc
Comm
Sensor Feedback
Current Sensor
Status
Current
Sensor
Circuitry
Gry
Gry
AXKT
CT
CLOSED
OPEN
AUTO
Org
Org
Selectable Jumper Wire
Wire Being
Monitored
Sensor Feedback
Current Sensor
Status
10-30 Vac/dc
Comm
CLOSED
OPEN
AUTO
Org*
Org*
Selectable Jumper Wire
*Org wires
will be Gry
10-30 Vac/dc
Comm
Sensor Feedback
Current Sensor
Status
Current
Sensor
Circuitry
CLOSED
OPEN
AUTO
Org
Org
Selectable Jumper Wire
Gry
Gry
AXGT
CT
Wire Being
Monitored
10-30 Vac/dc
Comm
V
V
0-10 Vdc
Comm
0-5 Vdc
CLOSED
OPEN
AUTO
Org*
Org*
Selectable Jumper Wire
*Org wires
will be Gry
Coil Current:
33 mA @ 10 Vac
35 mA @ 12 Vac
46 mA @ 24 Vac
55 mA @ 30 Vac
13 mA @ 10 Vdc
15 mA @ 12 Vdc
18 mA @ 24 Vdc
20 mA @ 30 Vdc
Coil Voltage Input:
10-30 Vac/dc ; 50-60 Hz
Drop Out = 2.1 Vac / 2.8 Vdc
Pull In = 9 Vac / 10 Vdc
RIBXLSA, RIBXLSF, (RIBXLSEA*)+
RIBXLSV, (RIBXLSEV*)^
RIBXLSRA, RIBXLSRF+
RIBXLSJA, RIBXLSJF+
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wire Length:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPST Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
20ms
Red LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V Rated
UL Listed, UL916, UL864, C-UL
California State Fire Marshal, CE, RoHS
UL Accepted for Use in Plenum, NEMA 1
Yes
Yes
RIBXLS Series
Enclosed Relay/AC Sensor Combinations, SPST + Override with 10-30 Vac/dc Coil
Notes:
• Normally Open or Normally Closed selected by yellow jumper wire
• Models AXKT and AXGT CT remotes do not have contact closure
circuitry and only work in conjunction with RIBXLSR and RIBXLSJ
models, respectively.
+ Sensor Contact:
• When current sensor status is o (open), leakage
<30 uA @ 30Vac/dc
• When current sensor status is on (closed), voltage drop
< .3 Vac/dc @ .1 Amp
< 1.6 Vac/dc @ .4 Amp
^ Sensor Feedback Output:
• Voltage output is proportional to current sensor range.
• Min. Input Impedance = 30K ohms
• Accuracy +/– 3% full scale
• Vripple < 10m Vac
RIBXLS SERIES SELECTION GUIDE
Model# Sensing Range Type * Threshold Sensor Output Remote Style Resistive Contact Ratings
RIBXLSF .50-10 Amps
Internal
w/ contact status
Fixed, .50 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
10 Amp
10 Amp Resistive @ 277 Vac
480 VA Pilot Duty @ 277 Vac
480 VA Ballast @ 277 Vac
Not rated for Electronic Ballast
600 Watt Tungsten @ 120 Vac (N/O)
240 Watt Tungsten @ 120 Vac (N/C)
1/3 HP @ 120-240 Vac (N/O)
1/6 HP @ 120-240 Vac (N/C)
1/4 HP @ 277 Vac (N/O)
1/8 HP @ 277 Vac (N/C)
RIBXLSA .50-10 Amps
Internal
w/ contact status
Adjustable
Solid State Contact
30 Vac/dc, 0.4 Amp
10 Amp
RIBXLSV 0-10 Amps
Internal
w/ voltage output
Analog
0-5 Vdc
0-10 Vdc
10 Amp
RIBXLSRF 1.25-150 Amps
External
w/ contact status
Fixed, 1.25 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
Model AXKT: (Solid
Core Remote)
10 Amp
RIBXLSRA 1.25-150 Amps
External
w/ contact status
Adjustable
Solid State Contact
30 Vac/dc, 0.4 Amp
Model AXKT: (Solid
Core Remote)
10 Amp
RIBXLSJF 3-150 Amps
External
w/ contact status
Fixed, 3 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
Model AXGT: (Split
Core Remote)
10 Amp
RIBXLSJA 3-150 Amps
External
w/ contact status
Adjustable
Solid State Contact
30 Vac/dc, 0.4 Amp
Model AXGT: (Split
Core Remote)
10 Amp
RIBXLSEA .125-5 Amps
Internal
w/ contact status
Adjustable
Solid State Contact
30 Vac/dc, 0.4 Amp
5 Amp
5 Amp Resistive @ 277 Vac
345 VA Pilot Duty @ 120/240 Vac (N/O)
268 VA Pilot Duty @ 277 Vac (N/O)
211 VA Pilot Duty @ 120/240 Vac (N/C)
175 VA Pilot Duty @ 277 Vac (N/C)
1/3 HP @ 120-240 Vac (N/O)
1/6 HP @ 120-240 Vac (N/C)
1/4 HP @ 277 Vac (N/O)
1/8 HP @ 277 Vac (N/C)
RIBXLSEV 0-5 Amps
Internal
w/ voltage output
Analog
0-5 Vdc
0-10 Vdc
5 Amp
* = Internal current sensor monitors current through common contact of relay.
RIBXLSA
RELAY & AC CURRENT SWITCH COMBOS
SPECIFICATIONS
Made in USA
Meets
“Buy American”
of ARRA 2009
FUNCTIONAL DEVICES CERTIFIED FOR USE WITH ECMS
ECMS
ECMS
ECMS
ECMS
ECMS
ECMS
= FDI Certied for use with electronically commutated motorsECMS