Cut Sheet

102815
RELAYS
(800) 888-5538 sales@functionaldevices.com www.functionaldevices.com
Blu
N/C
Yel
Comm
Org
N/O
Wht/Yel
Neutral or
Other Phase
Wht/Brn
208-277 Vac
24 Vac/dc
Com
Class 2 Dry Contact Binary Input
LON
LON
Service Button
GREEN LED = Network Status
PINK LED = Binary Input Status
RED LED = Relay Activated
YELLOW LED = Service
Closed Loop Actuator
(Binary Output)
(Binary Input)
Node Object
nvi Value
NV1
nvo Value Fb
NV2
nci Default
nci Max Receive T
Open Loop Sensor Object
nvo Value
NV1
nvi Request nvo Status
nci Invert
nci Max Send T
nci Min Send T
NV1 NV2
Blu
N/C
Yel
Comm
Org
N/O
Wht/Yel
Neutral
Wht/Blk
120 Vac
24 Vac/dc
Com
Class 2 Dry Contact Binary Input
LON
LON
Service Button
GREEN LED = Network Status
PINK LED = Binary Input Status
RED LED = Relay Activated
YELLOW LED = Service
Channel:
Transceiver Type:
Transceiver Compatibility:
Functional Blocks:
Downloadable Files:
TP/FT-10
FT5000 Smart Transceiver
FT3120 / FT3150, FTT-10 / FTT-10A, and
LPT-10 / LPT-11 Tranceivers
0000 Node Object
0004 Closed Loop Actuator Object
0001 Open Loop Sensor Object
PDF, XIF, APB, VSS and NXE
available on website.
The relay will go to the default state when the communication timer times out. Setting the timer value
to zero will cause the communication to never time out.
It is recommended to put a value in nci Max Send T to ensure the RIB re-synchronizes itself on the net-
work after power loss. It is the responsibility of the user to ensure this value does not cause conicts in
network trac. (No value = No “heartbeat updates / no re-sychronization; Low Value = Many updates
but may cause many trac collisions; High value = Few updates but many less collisions.)
DESCRIPTION SNVT NAME SNVT TYPE
Command to open/close relay nvi Value SNVT_switch
Command status of relay nvo Value Fb SNVT_switch
Default state of relay on/o nci Default SNVT_switch
Communication timer nci Max Receive T SNVT_elapsed_tm
Status of Binary Input nvo Value SNVT_switch
Invert status of Binary Input nci Invert SNVT_lev_disc
Max time between updates nci Max Send T SNVT_elapsed_tm
Min time between updates nci Min Send T SNVT_elapsed_tm
Notes:
Order with P1 option by adding “-P1” to end of
model number. The P1 option is pre-programmed to
allow dry contact binary input to command the relay.
Contact closure on the BI will activate relay.
When connecting 24 Vac to both the RIB(s) and a
half-wave device, damage to device can occur.
Option 1: Use separate transformers for each device.
Option 2: Add diode between devices, see Option 2
note below. ^^
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Green LED:
Red LED:
Yellow LED:
Pink LED:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
18ms
Network Status
Relay Status
Service Status
Binary Input Status
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V Rated
FCC, LonMark®, CE, RoHS
UL Listed, UL916, C-UL
UL Accepted for Use in Plenum, NEMA 1
No
No
Contact Ratings:
20 Amp Resistive @ 277 Vac
20 Amp Ballast @ 120/277 Vac (N/O)
20 Amp Ballast @ 277 Vac (N/C)
16 Amp Electronic Ballast @ 277 Vac (N/O)
10 Amp Tungsten @ 120 Vac (N/O)
1110 VA Pilot Duty @ 277 Vac
770 VA Pilot Duty @ 120 Vac
2 HP @ 277 Vac
1 HP @ 120 Vac
Power Input Ratings:
111 mA @ 24 Vac
96 mA @ 120 Vac (RIBTW2401B-LN)
105 mA @ 208-277 Vac (RIBTW2402B-LN)
81 mA @ 24 Vdc
Power Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz (RIBTW2401B-LN)
24 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIBTW2402B-LN)
RIBTW2401B-LN
LonWorks® Twisted-Pair FT-10 Network Enclosed
Dual I/O Device: One Binary Output (20 Amp
Relay SPDT), One Binary Input (Dry Contact
Class 2); 24 Vac/dc or 120 Vac Power Input
RIBTW2402B-LN
LonWorks®
Twisted-Pair FT-10 Network Enclosed
Dual I/O Device: One Binary Output (20 Amp
Relay SPDT), One Binary Input (Dry Contact
Class 2); 24 Vac/dc or 208-277 Vac Power Input
Closed Loop Actuator
(Binary Output)
(Binary Input)
Node Object
nvi Value
NV1
nvo Value Fb
NV2
nci Default
nci Max Receive T
Open Loop Sensor Object
nvo Value
NV1
nvi Request nvo Status
nci Invert
nci Max Send T
nci Min Send T
NV1 NV2
Closed Loop Actuator
(Binary Output)
(Binary Input)
Node Object
nvi Value
NV1
nvo Value Fb
NV2
nci Default
nci Max Receive T
Open Loop Sensor Object
nvo Value
NV1
nvi Request nvo Status
nci Invert
nci Max Send T
nci Min Send T
NV1 NV2
SPECIFICATIONS
NETWORK COMPATIBLE RELAYS
Half-Wave Device
RIBTW2401B-LN or RIBTW2402B-LN
Com
24 Vac/dc
Com
24 Vac
24 Vac
IN4004
Add diode on 24 Vac power (Com) interconnection
between devices. Band on diode faces towards RIB(s).
^^ Option 2:
Made in USA
Meets
Buy American
of ARRA 2009

Summary of content (1 pages)