Cut Sheet
Voltage Recommended
Application
Functional
Devices Model
O Delay Recommended Door
Contact *
Wiring Conguration Wiring
Diagram
120 Vac
Retrot CLC106 None 1 ACLCMAG Included 1 CLC106 per door, wired in Parallel Fig. A
New Construction
CLC212 None Form C contact 1 contact per door, wired in Parallel Fig. B
CLC212-D15 15 min. ACLCMAG 1 contact per door, wired in Series Fig. C
CLC212-D60 60 min. ACLCMAG 1 contact per door, wired in Series Fig. C
277 Vac New Construction
CLC212 None Form C contact 1 contact per door, wired in Parallel Fig. B
CLC212-D15 15 min. ACLCMAG 1 contact per door, wired in Series Fig. C
CLC212-D60 60 min. ACLCMAG 1 contact per door, wired in Series Fig. C
Closet Light Controller Selection Guide for Dual-Door Closets
Use two models CLC106, wired in parallel.
Figure A
Magnetic Switch
(included)
Magnetic Switch
(included)
Red
Red
Neutral
Neutral
CLC106
CLC106
120 Vac
Blk Wht
Blk Wht
“Form C” door switches wired in parallel.
Figure B
Blk
Wht
120 to 277 Vac
Neutral or Other Phase
CLC212
Red
Neutral or Other Phase
Wht/Blu
Wht/Red
Model ACLCMAG door switches wired in series
Figure C
Blk
Wht
120 to 277 Vac
Neutral or Other Phase
CLC212-D60
CLC212-D15
or
Red
Neutral or Other Phase
Wht/Blu
Wht/Red
A1663A • 01.29.13
* Details for Recommended Door Contact:
Form C contact (Provided by customer. For use with CLC212): A Form C door contact is a SPDT switch with one N/O connection,
one N/C connection, and one COM (shared) connection. In order for model CLC212 to properly function, the Form C switch
must be wired so that its contacts CLOSE when the door is OPEN. When the door is OPEN, the light will turn ON. Functional
Devices recommends a Form C contact to avoid confusion between the alarm and controls industries’ denitions of Normally
Open and Normally Closed.
ACLCMAG (Available from Functional Devices. For use with CLC212-D15 and CLC212-D60): Model ACLCMAG is a magnetic door
switch that OPENS its contacts when the closet door is OPEN. When the door is OPEN, the light will turn ON.
Always follow NEC® and local codes. Functional Devices, Inc.
recommends adding a label on each device used in this
application with the message: “WARNING – LOAD SIDE
TERMINALS MAY BE ENERGIZED BY BACKFEED,” similar to
what is recommended in NEC® Article 404.6 (C) 2008.