Cut Sheet

Functional Devices, Inc. • p: 800.888.5538 • f: 765.883.7505 • www.functionaldevices.com/lighting-controls • sales@functionaldevices.com
Closet
Light
CLC212
Light Fixture
Junction Box
Class II Wiring
N/C
Dry Contact
Door Switch
(not included)
Closet
Door
120 Vac
Power
Class II Wiring
Blk
Wht
Red
Line
Neutral
Light Fixture
Junction Box
CLC212
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPST-N/O Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
LED On = Activated
1.70˝ x 2.80˝ x 1.50˝ with .50˝ NPT Nipple
16˝, 600V Rated
UL Listed, UL916, C-UL, CE
UL Accepted for Use in Plenum, NEMA 1
No
No
Contact Ratings:
10 Amp General Use @ 277 Vac
1/2 HP @ 125 Vac
1 HP @ 250 Vac
1/4 HP @ 277 Vac
470 VA Pilot Duty @ 125 Vac
770 VA Pilot Duty @ 250 Vac
Power Usage:
50 mA @ 240 Vac Max.
Red
Control
Circuit
Blk
120 to 277 Vac
Wht
Neutral or Other Phase
Dry Contact Input
Wht/Red
Wht/Blu
Notes:
Dry Contact Input Operation: Close Wht/Red wire to
Wht/Blu wire to activate relay. Normally open relay
will close. If more than one CLC212 shares a single
dry contact input, Wht/Blu must be common.
Order Normally Closed contact by adding “-NC to end
of model number for opposite operation. Normally
closed will open when Wht/Red wire is closed to
Wht/Blu wire.
• Switch must be Form C or N/C.
• Suggested switches: Detex® model MS-2049 or similar
• No stepdown transformer necessary
• Operates on any device from 120 Vac
to 277 Vac
• Light 18 AWG wire used to control relay,
instead of armored cable, but any size
may be used
• Closet light turns on when door is open
• Customer needs to purchase Form C or
N/C door switch.
A Normally Closed (N/C) door switch is closed
when no outside forces are acting upon it.
When used in this application, the switch is open
when the door is closed, and the switch closes
when the door is opened, activating the
controller to turn the light on.
(Door switch not provided, see notes for details.)
New Construction Applications
Made in USA
Meets
Buy American
of ARRA 2009
CLC212
Enclosed Relay 10 Amp SPST-N/O, Separated Class 2 Dry Contact Input, 120-277 Vac Power
Specications
Closet Light Controller