Cut Sheet
Phone: (800) 888-5538 • Fax: (765) 883-7505 • www.functionaldevices.com • sales@functionaldevices.com
022916
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPST-N/O Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
LED On = Activated
1.70˝ x 2.80˝ x 1.50˝ with .50˝ NPT Nipple
16˝, 600V Rated
UL Listed, UL916, C-UL, CE
UL Accepted for Use in Plenum, NEMA 1
No
No
Contact Ratings:
10 Amp General Use @ 277 Vac
1/2 HP @ 125 Vac
1 HP @ 250 Vac
1/4 HP @ 277 Vac
470 VA Pilot Duty @ 125 Vac
770 VA Pilot Duty @ 250 Vac
Power Usage:
52 mA @ 277 Vac Max.
Red
Control
Circuit
Blk
120 to 277 Vac
Wht
Neutral or Other Phase
Dry Contact Input
Wht/Red
Wht/Blu
Notes:
• Dry Contact Input Operation: Open Wht/Red wire and
Wht/Blu wire to activate relay. Relay contact will close.
If more than one CLC212-D15 shares a single dry
contact input, Wht/Blu must be common.
• For 60 minute delay, order model CLC212-D60.
• Suggested switches:
Functional Devices models ACLCMAGSM or
ACLCMAGDJ
New Construction Applications
Made in USA
Meets
“Buy American”
of ARRA 2009
CLC212-D15
Enclosed Relay 10 Amp SPST-N/O, Separated Class 2 Dry Contact Input, 120-277 Vac Power
• No stepdown transformer necessary
• 15 minute delay when door is left open
• Operates on any device from 120 Vac
to 277 Vac
• Light 18 AWG wire used to control
relay, instead of armored cable, but
any size may be used
• Closet light turns on when door is open
• Customer needs to purchase
Form C or N/O door switch
A Normally Open (N/O) door switch is open
when no outside forces are acting upon it.
When used in this application, the switch is
closed when the door is closed, and the switch
opens when the door is opened, activating the
controller to turn the light on.
(Door switch not provided, see notes for details.)
With the CLC212-D15, money and energy can be saved when a closet door is inadvertently left open. In
this event, the closet light will switch o after a 15 minute delay. If you wish the light to remain on after
the door is open, you simply open, close and reopen the door within three seconds.
CLOSET LIGHT CONTROLLER
Specications
Closet
Light
CLC212-D15
Light Fixture
Junction Box
Class II Wiring
N/O
Dry-Contact
Door Switch
(Not included)
Closet
Door
120 Vac
Power
Class II Wiring
Blk
Wht
Red
Line
Neutral
Light Fixture
Junction Box
CLC212-D15