OPERATION PHW-IOM-2013-0214 SECTION 3
3-4
! WARNING
Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full
review of documentation available
from the component manufacturer.
4 CAUTION
After checking controls by manual
adjustment, make sure they are always
reset to their proper settings.
When making changes to the controls
pro le, a combustion analyzer is
required.
Check daily that the equipment area
is free and clear of any combustible
materials, including ammable vapors
and liquids.
Water chemistry in the boiler must be
kept within required limits. Failure to
do so may cause premature pressure
vessel failure and will void the warranty.
} LINKAGE RELATIONSHIPS
The location of the linkage rods and the speed at which the butter y gas valve
and butter y exhaust valve opens or closes will determine whether the unit
operates smoothly or not.
} GAS BUTTERFLY VALVE SIDE
The longer the radius on the mod motor pivot arm, the quicker the gas butter y
valve shuts o . Conversely, the shorter the radius the slower the gas butter y
valve shuts o . The longer the radius on the gas valve pivot arm, the slower the
gas butter y valve shuts o . Conversely, the shorter the radius the quicker the
gas butter y valve shuts o .
} EXHAUST BUTTERFLY VALVE SIDE
1. The longer the radius on the mod motor pivot arm, the quicker the exhaust
butter y valve shuts o . Conversely, the shorter the radius the slower the
exhaust butter y valve shuts o .
2. The longer the radius on the exhaust valve pivot arm, the slower the
exhaust butter y valve shuts o . Conversely, the shorter the radius the
quicker the exhaust butter y valve shuts o .
3. At High Fire the linkage arms should NOT begin or nish travel in the
vertical position. If this occurs there is a possibility that the gears will bind
and cause damage to the mod motor.
4. The gas pressure regulator is the only means for adjusting High Fire input
to the factory test re values. After the boiler is operated at High Fire to the
desired settings, proceed to operate at Low Fire.
5. Before the boiler res at high  re:
§ Access Status screen on SOLA Control and press Operation.
§ Press yellow box next to Firing Rate.
§ Change Automatic to Manual in Run, and key in 100%. Press OK. Refer to
Figure 25.
FIGURE 25  EDIT THE FIRING RATE