User Manual

Operation
Operating Parameters
PID Functions
SYMBOL DESCRIPTION DEFAULT VALUE FULTON VALUE CUSTOMER VALUE
AL1 Alarm 1 Setting 100 5
AL2 Alarm 2 Setting 0 0
AL3 Alarm 3 Setting 100 0
AT Auto-Tune off off
SC Super Function On/Off off off
SP.no Target Setpoint 11
Pld PID Parameter 0 Enter 1 for PID Menu then 0
FL PV Input Filter off 0
BS PV Input Bias eus (0.0%) 0
UPR Rising Value Setting off off
DNR Descending Gradient off off
OH Output High Limit 100 100
OL Output Low Limit 00
H Hysteresis On/Off 0.10% 0.10%
DR Direct/Reverse Action 00
HB1 Heater Disconnect off off
HB2 Heater Disconnect off off
HC1 Heater Disconnect off off
HC2 Heater Disconnect off off
ORB On/Off Rate Detection eus (1.0%) 0
ORH On/Off Rate Upper Limit 100 100
ORL On/Off Rate Lower Limit 00
OR On/Off Rate 00
1.SP Target Setpoint 1 00
2.SP Target Setpoint 2 00
3.SP Target Setpoint 2 00
4.SP Target Setpoint 4 00
Note: Parameters with bold values only will be used.
SYMBOL DESCRIPTION DEFAULT VALUE FULTON VALUE CUSTOMER VALUE
1.P Proportional Band 510
1.l Integral 240 off
1.d Derivative off off
1.MR Manual Reset 60 0
1.Pc Proportional Band 5 5
1.lc Integral Time 240 240
1.Dc Derivative Time 60 60
1.DB Dead Band 3 3
1.RP Reference Point 1 100 100
2.RP Reference Point 2 100 100
RDV Reference Deviation 0.5 0.5
Note: Parameters with bold values only will be used.
32-PDWH