Owner's manual
Specifications
Models ICS/ICX/FB 9.5 10 15 20 25 30
Boiler Connections
N. Steam Outlet 15 PSI N/A 1.5” 2” 3” 3” 3”
NPT NPT CL150# CL150# CL150#
Flange Flange Flange
N. Steam Outlet 150 PSI 1” 1” 1.25” 1.5” 2” 2”
NPT NPT NPT NPT NPT NPT
O. Safety Valve Outlet 15 PSI IN N/A 0.75 1 1.5 1.5 1.5
MM 19 32 38 38 38
O. Safety Valve Outlet 150 PSI+ IN 1 1 1 1 1 1
(9.5 HP 100 PSI) MM 25 25 25 25 25 25
P. Safety Valve Inlet 15 PSI++ IN N/A 0.75 1 1.25 1.25 1.25
MM 19 25 32 32 32
P. Safety Valve Inlet 150 PSI IN 0.75 0.75 0.75 0.75 0.75 0.75
(9.5 HP 100 PSI) MM 19 19 19 19 19 19
Q. Feedwater Inlet IN 1 1 1 1 1 1
MM 25 25 25 25 25 25
R. Blowdown Outlet IN 1 1 1 1.25 1.25 1.25
MM 25 25 25 32 32 32
S. Water Column Blowdown IN 1 1 1 1 1 1
MM 25 25 25 25 25 25
Ratings* (Sea level to 3000 ft.)
Output 1000 BTU/HR 318 335 503 670 838 1005
1000 KCAL/HR 80.1 84.4 127 169 211 253
Steam Output LB/HR 328 345 518 690 863 1035
KG/HR 149 157 235 313 392 470
Approximate Fuel Consumption at Rated Capacity+++
Natural Gas (ICS) FT3/HR 398 419 628 837 1047 1256
(9” - 13” w.c. req’d) M3/HR 11.3 11.9 17.8 23.7 29.7 35.4
Natural Gas (ICX) FT3/HR 384 403 606 807 1009 1210
(9” - 13” w.c. req’d) M3/HR 10.8 11.4 17.2 22.9 28.6 34.3
Natural Gas Boiler IN 1 1 1 1.25 1.25 1.5
Connection Size (Std CSD-1) MM 25 25 25 32 32 38
Oil Inlet Size IN 1/4 1/4 1/4 1/4 1/4 1/4
MM 6 6 6 6 6 6
Burner 3450 RPM/60 CY
Motor HP 2850 RPM/50 CY .75 .75 1.5 1.5 1.5 1.5
Electric Power Requirements - Burner Only (in Amps) ***
120V,60 CY, 1 Phase 9.2 9.2 -- -- -- --
240V, 50/60 CY, 1 Phase 4.6 4.6 8.9 8.9 8.9 8.9
208V, 50/60 CY, 3 Phase 3.1 3.1 4.4 4.4 4.4 4.4
240V, 50/60 CY, 3 Phase 2.8 2.8 4.2 4.2 4.2 4.2
480V, 50/60 CY, 3 Phase 1.4 1.4 2.1 2.1 2.1 2.1
Water Content
U.S. GAL 16 24 39 77 82 170
LITERS 61 91 148 292 311 644
Specifications and Dimensions are approximate. We reserve the right to change specifications and/or dimensions..+ High pressure boilers purchased with low pressure
openings may have larger than specified opening sizes, consult factory for correct opening sizes.++ 50 and 60 HP have two safety valves on low pressure.
+++Consumption based on Natural Gas 1000 BTU/ft.
3
. *All ratings from 0 PSIG and at 212 degrees F. *** Control circuit electrical requirement will vary with the system
voltage, please consult factory. --Consult factory.