User guide

© The Fulton Companies 2014
INSTALLATION CAL-IOM-2014-0129 SECTION 2
2-4
TABLE 1  OPERATING REQUIREMENTS SEE TABLE NOTES ON PAGE 25
Caliber Model Size
300 500 750 850
Input (BTU/Hr)
300,000 500,000 750,000 850,000
Output (BTU/Hr)
283,500 472,500 708,750 803,250
Natural Gas Consumption (ft3/hr)
297 495 743 842
Propane Consumption**(ft3/hr)
120 200 300 340
Gas Supply Pressure Minimum
Maximum
4.0
14
4.0
14
4.0
14
4.0
14
Dry Weight LB
KG
500 630 719 729
227 286 326 331
Operating Weight LB
KG
518 662 757 772
235 300 343 350
Control Voltage (V/Hz/Ph)
120/60/1
Blower Voltage (V/Hz/Ph)
120/60/1
X. Electrical Connection*
120/60/1
Y. Condensate Drain Connection* IN
MM
0.75 .075 0.75 0.75
19 19 19 19
Amp Draw
2.1 3.6 3.6 3.6
I. Gas Connection* IN
MM
.75 1 1.25 1.25
19.0 25.4 31.75 31.75
G. Water Inlet/Outlet Connection* IN
MM
1.25 1.5 2 2
31.75 38.1 50.8 50.8
J. Flue Connection (ID)* IN
MM
4.25 4.25 5.875 5.875
108 108 149 149
H. Air Intake Connection***(OD) IN
MM
4.5 4.5 4.5 4.5
114 114 114 114
A. Boiler Width (including feet)* IN
MM
34.5 34.5 34.5 34.5
876 876 876 876
B. Boiler Height* IN
MM
51.6 51.6 51.6 51.6
1310 1310 1310 1310
C. Boiler Depth (Cabinet)* IN
MM
31.25 44 57.25 57.25
793 1117 1454 1454