User Guide

Table Of Contents
Fulham Co. Inc.: 12705 South Van Ness Ave., Hawthorne, CA 90250 Tel.: 1-323-779-2980 Fax.: 1-323-754-9060.
Specifications subject to change without notice.
order@fulham.com
www.fulham.com
Page 3 of 3
2023-926 Rev A
ELMOPLX00SR
Remote Control Instructions
Memory Mode (Commissioning)
To begin commissioning follow the steps bellow:
1. Select either A, B, C, D.
2. Indicator lights on the remote will flash to indicate the current saved settings.
3. Settings can be configured by pressing the appropriate buttons in the high lighted gray area of the remote control.
(TRIM-LEVEL, SENSITIVITY, HOLD TIME, DIM, STANDBY TIME and PHOTOCELL). Review selections and make changes as necessary.
4. Point the IR remote control in the direction of the desired luminaire for configuration and press “SEND”.
5. If the configuration was successful, the luminaire will flash two times confirming the settings have been saved successfully. Any parameter
change to the current saved settings on A through D will override previous settings and will be automatically saved on the remote.
If configuring multiple luminaires, select the configured memory mode A through D then follow steps 4 and 5.
*** E MODE allows visual adjustment to choose the desired dimming level.
Continuous Adjustment Mode or Daylight Harvesting (F Mode) enables dimmability in response to daylight availability.
1. Point the IR remote control in the direction of the desired luminaire.
2. Press “ON” then press “Dim+” or “DIM-” to adjust the dimming level.
3. Press “F”. the indicator lights on the remote control will indicate current saved settings.
Note: Only TRIM-LEVEL, SENSITIVITY and HOLD TIME can be selected for Daylight Harvesting settings.
4. Review selected settings and make changes as necessary. press “SEND”.
5. If the configuration was successful, the luminaire will flash two times confirming the settings have been saved successfully.
If configuring multiple luminaires, select the configured DAYLIGHT HARVESTING setting then follow steps 4 and 5.
Remote Control Function Chart
Reset Mode
Default Settings: Motion---> 100%; No Motion for 5 min---> dim to 30%; No motion for 60 min---> Off
Specifications
Communication Method
Battery Type
Flame Rating
Infrared
3V CR2032 Batteries (Qty. 2)
HB
Operating Humidity
≤90% RH
Operating Temperature 0°C - 45°C (32°F - 113°F)
Mechanical Drawing
Unit: mm/inch