Submittal

Variable Refrigerant Flow System
Submittal Data: UTZ-VXAA Compact Cassette Fresh Air Intake kitSubmittal Data: UTZ-VXAA Compact Cassette Fresh Air Intake kit
Job Name:______________________________ Date:_______________________________
Location:_______________________________ Approval:____________________________
Engineer:_______________________________ Construction:_________________________
Submitted to:____________________________ Unit #:______________________________
Submitted by:___________________________ Drawing #:___________________________
Reference:______________________________
Fujitsu General America, Inc.
353 Route 46 West
Fairfield, NJ 07004
Toll Free: 1-888-888-3424
Fax: (973) 836-0447
www.airstagevrf.com
General Features
Fresh Air can be added to the system with this Fresh Air kit for
compact cassettes to increase the indoor air quality by diluting
polluted or stale indoor air.
1 of 2
Rev. date 02/11/16
Compatibility
Compatible models…………………………………………………. AUUA7TLAV
AUUA9TLAV
AUUA12TLAV
AUUA14TLAV
AUUA18TLAV
AUUA24TLAV
Fresh Air Intake
Max fresh air intake volume………………………………….…….. 10% (for high)
Connection
Connection duct type In(mm)……………………………………. 3-15/16 (100)
Dimensions
H x W x D
Net In(mm)…………...…....….…. 4-3/4 x 22-7/16 x 22-7/16 (120 x 570 x 570)
Gross In(mm).....…………….......…. 6-1/2 x 23-1/16 x 23-1/16 (165 x 585 x 585)
Weight
Net…………………..……………..…………………….................... 3.5 lbs. (8 kg)
Gross………………..…….…….……………………………...….... 5.5 lbs. (12 kg)
Air Flow
Restrictions
Be careful when installing fresh air kit in coastal areas. The salt in
the air can cause unit corrosion and unit failure.
Areas that generate corrosive gases such as sulfuric acid, chlorine
gas and alkalis will cause corrosion and refrigerant leaks.
Do not induce air below 32°F (0°C). The low temperature and
high humidity can cause excessive condensation.

Summary of content (2 pages)