Service Manual
Indoor unit field setting
setting by
remote controller
Setting Mode
ITEM
CODE No.
ITEM
CODE No.
Setting Function DefaultClassification
30
Correction
01
00Cool air temperature trigger
02
Default 0
°F(0°C)
Temperature overshoot setting +4°F(+2°C)
Temperature undershoot setting -4°F(-2°C)
Default 0°F(0°C)
Temperature undershoot setting -11°F(-6°C)
Temperature slightly unbdershoot setting -7°F(-4°C)
Temperature overshoot setting +7°F(+4°C)
31
Heat air temperature trigger 00
01
02
03
40
Auto restart *1 00 Enable
01 Disable
43
Cool air prevention 00 Super low
01
Follow the setting on the remote controller
46
External control 00
Start / Stop
01 Emergency stop
47
Error report target 00
All
01 Display only for central remote control
02 Forced stop (Start/Stop by RC is restricted)
49
FAN Setting when cooling thermo-
stat OFF *2
01
00
Follow the setting on the remote controller
Forced stop
60
Switching functions for external
inputs and external outputs
terminals
00
01
02
04
05
03
07
08
06
Mode 0
Mode 1
Mode 2
Mode 3
Mode 4
Mode 5
Mode 6
Mode 7
Mode 8
61
Control switching of external
heaters
(Except Compact wall mounted
and Wall mounted )
62
Operating temperature switching of
external heaters
(Except Compact wall mounted
and Wall mounted )
00
01
02
04
00
03
02
03
04
05
01
Auxiliary heater control 1
Auxiliary heater control 2
Heat pump prohibition control
Heater selection control using outdoor temperature 1
Heater selection control using outdoor temperature 2
Setting 0
Setting 1
Setting 2
Setting 3
Setting 4
Setting 5
Change of
function 1
Change of
function 2
*1: Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Fan Setting when cooling thermostat OFF, Connection of the wired remote controller (2-wire type or 3-wire type) and switching its thermistor are necessary.
01-26