Service Manual

Rush Current Limiting Resistor
Temp Rise Protection
Inverter PCB
1. Magnetic relay (for INV) coil side wiring disconnection, open
2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
3. Magnetic relay activation circuit defective
4. Main PCB to Inverter PCB wiring disconnection, open
5. Main PCB output AC208- 230V on CN130 defective
Main PCB defective (output AC208- 230V on CN130 for Magnetic relay (INV) defective)
"Protection stop by "Rush current limiting resistor temperature rise detection''
of inverter PCB" was generated 2 times.
OK
OK
OK
Check Point 1 : Check the magnetic relay (for invertert) coil side wiring
Connector and wiring connection state check
Cable open check
Cable open check
Check Point 2 : Check Power supply to Filter PCB (INV) to inverter PCB wiring
Connector and wiring connection state check
Check Point 3-1 : Magnetic relay activation circuit
Chack the DC Voltage (12V) of CN330 on INVERTER PCB
Check Point 5 : Main PCB output AC208- 230V for Magnetic relay
Check the AC208- 230V of CN130 on Main PCB
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 6 8. 2
Error Code : 9 U / 6 8
Trouble shooting 33 E68. 2
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
OK
OK
Check Point 4 : Check the wiring (Main PCB to Inverter PCB)
Replace Inverter PCB
NG
Check the wiring connection.
(CN138 on Main PCB to CN330 on Inverter PCB)
Check Point 6 : Replace Main PCB
Change Main PCB and set up the original address.
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-42