Installation Manual

* When using the “UTZ-KXGC” kit for high humidity, please rst cut off and
remove the heat insulation as shown in the gure.
Please install the kit for high
-
humidity according to the installation
instruction sheet provided.
30 (1-3/16)
Unit: mm (in.)
80 (3-5/32)
cut off
7. DUCT INSTALLATION
7.1. Pre-installation preparations
CAUTION
Procure a duct with internal diameter that ts the external diameter of the
duct ange.
Please note that regulations of some countries may require the use of a
nonammable duct.
If the duct penetrates a re-retarding division or other re-proong
measures, the installation of re dampers, or a construction that does
not adversely affect re control measures is a regulatory requirement of
some countries.
When using metallic ducts please ensure metals (i.e., metal lath, wire
lath, stainless sheeting) are electrically insulated.
(A short occurring by electrical connection can cause re)
Please ensure to thermally insulate connected ducts to prevent
condensation.
Please make certain that netting or other measures are installed in parts
exposed to the outside air to prevent inltration of small animals such as
birds and insects.
Please be certain to install external air lters to parts exposed to the
outside air for heat exchanger protection of indoor equipment.
Please avoid the inltration of rain water by installing outside ducts with
an incline of at least 1/30, and tting hoods on openings.
Be certain to use electric dampers and shutters to avoid inltration of
cold air, wind and fog during shutdown in areas with cold climates, strong
winds, or where fogs are common.
7.2. Duct installation
Please fasten the connecting parts of the ducts with bands, and wrap with
vinyl tape to ensure no air leaks.
(Carry out the work to ensure no air leakage at a pressure of 200 Pa (0.03 psi))
Please do not construct the duct in the manner of below.
l
Extreme Bends
l
Highly Repetitive Bends
l
Making the Connecting Duct Diameters Smaller
Completion gure
Band (eld supplied)
Vinyl tape (eld supplied)
Duct (eld supplied)
Indoor Unit
Hanging band for duct
(eld supplied)
Fresh Air
Intake Kit
When wiring of the duct fan is required please refer to “9. WIRING THE
DUCT FAN”.
8. DECORATION PANEL INSTALLATION
8.1. Installation of decoration panel
(1) Please connect extension wires for use with louvers, or extension wire
for optical receiver after provisional securing of the decoration panels.
(2) Tie the wires together with the cable tie provided and insert into the hole
of the Fresh Air Intake Kit.
(3) Install the wire-cover provided on the Fresh Air Intake Kit
(4) Please install decoration panel according to the installation instruction
sheet provided.
Metal ttings × 2
Screw × 2
Connect
Extension wire × 3
Cable tie
l
Connection diagram
For Relay Output voltage : DC12 ± 2
V
Permissible current : 50 mA
P.C.B
Indoor
unit
25m *
(82ft.)
Field supply
Relay
Fuse
Power
Fan, other
CNB01
*:Make the distance from the PC board to the Relay Unit within 25 m (82 ft.).
l
Indoor unit status
stop
operation
12 V
Indoor
unit fan
CNB01(1-4)
(output)
0 V
l
Wire (External output
3
)
Wire color: RED
1
2
3
4
5
6
Wire color: WHITE
9.2. Connection methods
Wire modication
Use a tool to cut off the terminal on the end of the wire, and then remove
the insulation from the cut end of the wire.
Connect the wire with connecting wire with solder.
IMPORTANT: Be sure to insulate the connection between the wires.
Field supply
Solder and insulate the connected parts.
Option parts:
External input /output wire
• Connection terminals and wiring arrangement
TYPE 1
[Single & Multi]
Through-hole
CN6
TYPE 2
[
VRF (AUXB
**
LALH)
]
CN16
TYPE 3
[
VRF (AUXB
**
G
*
LH)
]
CNB01
9. WIRING THE DUCT FAN
9.1. Pre-installation preparations
Make eld supplied arrangements for duct fan and drive relay.
Connect the relay with the wire provided for use as an external power
output
CAUTION
Wiring of the external power output varies with equipment model.
(1) TYPE 1 [Single & Multi]
You can control duct fan by synchronization with fan operation of indoor
unit.
Wire for fresh air control output is supplied with Fresh Air Intake Kit.
Extended length of the wire : For Single & Multi split system : Max. 10 m (32 ft.)
l
Connection diagram
For Relay Output voltage : DC12V ± 2 V
Permissible current : 15 mA
P.C.B
Indoor
unit
10m *
(32ft.)
Field supply
Relay
Fuse
Power
Fan, other
CN6
*:Make the distance from the PC board to the Relay Unit within 10 m (32 ft.).
l
Indoor unit status
stop
operation
12 V
Indoor
unit fan
CN6
(output)
0 V
l
Wire (External output
1
)
Wire color: RED
Wire color: WHITE
1
2
(2) TYPE 2 [VRF(AUXB
**
LALH)]
You can control duct fan by synchronization with fan operation of indoor
unit.
Wire for fresh air control output is supplied with Fresh Air Intake Kit.
Extended length of the wire : For VRF system Max. 150m (490 ft.)
l
Connection diagram
For Relay Output voltage : DC12 - 24 V
Permissible current : 30 mA
P.C.B
Indoor
unit
150m
*
(490ft.)
Field supply
Relay
Fuse
Power
Fan, other
CN16
DC 12-24 V
*:Make the distance from the PC board to the Relay Unit within 150 m (492 ft.).
l
Indoor unit status
stop
operation
12-24 V
Indoor
unit fan
CN16
(output)
0 V
l
Wire (External output
2
)
Wire color: RED
1
2
3
4
Wire color: WHITE
(3) TYPE 3 [VRF(AUXB
**
G
*
LH)]
You can control duct fan by synchronization with fan operation of indoor
unit.
Wire for fresh air control output is supplied with Fresh Air Intake Kit.
Extended length of the wire : For VRF system Max. 25m (82 ft.)
9379477031-01_IM_EN_130307.indd 2 2013/03/18 18:07:56