Installation Manual

FRESH AIR INTAKE KIT
INSTALLATION MANUAL
For authorized service personnel only.
UTZ-VXAA
1.
SAFETY PRECAUTIONS
Be sure to read this Manual thoroughly before installation.
The warnings and precautions indicated in this Manual contain important
information pertaining to your safety. Be sure to observe them.
Hand this Manual to the customer. Request the customer to keep them on
hand for future use, such as for relocating or repairing the unit.
WARNING
This mark indicates procedures which, if improperly
performed, might lead to the death or serious injury
of the user.
Request your dealer or a professional installer to install the indoor unit
in accordance with this Installation Manual. An improperly installed unit
can cause serious accidents such as water leakage, electric shock, or
re. If the indoor unit is installed in disregard of the instructions in the
Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning
ON the power before the work is completed can cause serious accidents
such as electric shock or re.
Installation work must be performed in accordance with national wiring
standards by authorized personnel only.
CAUTION
This mark indicates procedures which, if improperly
performed, might possibly result in personal harm
to the user, or damage to property.
2.
ABOUT THE UNIT
2.1. Precautions for fresh air intake
l
The Fresh Air Intake Kit can be installed onto cassette type air
conditioners.
l
On installation please also refer to the air conditioner installation manual
and decoration panel installation manual.
l
The volume of ventilated air provided by the Fresh Air Intake Kit may be
unable to fulll ventilation regulations in all countries.
On such occasions we ask that this kit be used along with Energy
recovery ventilators.
l
When intaking outside air please ensure correct air-conditioning design
as based on air-conditioning load calculations.
As outside air is not being processed an increase in outside air load can
affect air conditioning.
l
When installing the duct fan, connect the drive relay (eld supplied) and
operate with the indoor unit.
Please ensure the intake air volume is below 10% of the product’s air
volume HI.
When the intaken air volume becomes too large there the operating noise
may increase and room temperature detection may be affected.
l
Condensation may form on the product when outside air temperature is
low, and the temperature and humidity surrounding the product are high.
Don’t intake the air of below 0˚(32°F) into the Fresh Air Intake Kit.
The upper limit of the product’s temperature range should respond to the
outdoor temperature range.
l
Please ensure the product is installed a distance of at least 3 times the
duct diameter away from exterior wall air inlets, or air exhausts for the
prevention of short circuits.
2.2. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the
manufacturer or other prescribed parts. The use of non-prescribed parts
can cause serious accidents such as the unit falling, water leakage,
electric shock, or re.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other
accessories until the installation work has been completed.
Name and Shape Q’ty Application
Chamber
1
Air joint for connecting duct
Wire cover
1
Cover for extension wire
Screw
4
Attaching for chamber
Attaching for wire cover
Extension wire for louver
white
red
2
Extension wire for louver
Extension wire for receiver
1
Extension wire for receiver
Wire (External output 1)
1
For connect indoor unit to relay
of duct fan
Wire (External output 2)
1
For connect indoor unit to relay
of duct fan
Wire (External output 3)
1
For connect indoor unit to relay
of duct fan
Bolt
4
For attaching the kit to indoor
unit
Cable tie
1
For xing wire
3.
INSTALLATION WORK
3.1. Selecting an installation location
CAUTION
Do not install the unit in the following areas:
Area with high salt content, such as at the seaside. It will deteriorate
metal parts, causing the parts to fall or the unit to leak water.
Area lled with mineral oil or containing a large amount of splashed oil
or steam, such as a kitchen. It will deteriorate plastic parts, causing the
parts to fall or the unit to leak water.
Area that generates substances that adversely affect the equipment, such
as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes
and brazed joints to corrode, which can cause refrigerant leakage.
Area that can cause combustible gas to leak, contains suspended
carbon bers or ammable dust, or volatile inammables such as paint
thinner or gasoline. If gas leaks and settles around the unit, it can cause
a re.
5.
INSTALLATION OF THE FRESH AIR INTAKE KIT
5.1. Provisional attachment
CAUTION
Installing the Fresh Air Intake Kit with the wrong direction is a cause of
water leakage.
Provisionally attach the “DRAIN”, “PIPE” of the Fresh Air Intake Kit to the
indoor unit foam-sealed DRAIN”, PIPE, following the direction of the
indoor unit, using the metal ttings of the combined diagram.
Bolt ×4
“DRAIN”
“DRAIN”
“PIPE”
“PIPE”
Metal ttings×2
5.2. Attaching the fresh air intake kit
Attach the Fresh Air Intake Kit to the main body using the bolts provided.
6. CHAMBER INSTALLATION
Fit the four-sided holes of the chamber together with the hook ttings of the
Fresh Air Intake Kit (in 2 places), and secure the attached chamber in place
with screws provided.
Ø100 (3-15/16)
hook ttings
screw × 2
3.2. Installation dimension location
WARNING
Install the air conditioner in a location which can withstand a load of at
least ve times the weight of the main unit and which will not amplify
sound or vibration. If the installation location is not strong enough, the
indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will
come loose. Please take care.
Indoor Unit
(12-7/32)
310
duct (eld supplied)
Unit: mm (in.)
390 (15-11/32)
Fresh Air Intake Kit
Ceiling opening space
Inspection hatch
*1
*1:
Suspend the parts securely. Due to the weight of the indoor unit and this
kit, a gap may form between them.
150 to 200
( 5-7/8 to 7-7/8)
Inspection hatch *2
Unit: mm (in.)
Min.450 (17-3/4)
*2: Please install the access ports
(more than 450×450 mm (17-3/4 ×17-3/4 in.)).
4. MOUNTING THE INDOOR UNIT MAIN BODY
4.1. Pre-installation preparations
When the number of air outlets is to change, a separately-sold air-outlet
sealing material should be fitted to the indoor unit main body prior to
installing the Fresh Air Intake Kit.
4.2. Mounting of indoor unit
Please refer to the installation manual provided with the indoor unit for
mounting.
Please refer to the diagram below for installation height.
When installing this product to existing indoor units, please adjust
the installation height of the indoor units to height 240 to 245 mm
(9-7/16 to 9-21/32 in.).
Indoor Unit
240 to 245
(9-7/16 to 9-21/32)
Fresh Air
Intake Kit
ceiling
Metal Hanging Fastener
Unit: mm (in.)
(PART NO. 9379477031)
9379477031-01_IM_EN_130307.indd 1 2013/03/18 18:07:43