Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
1-4-2. EXTERNAL OUTPUT
Connector Output voltage Status
CN410
(Black)
Ch1 0 V All of indoor units "Stop"
Pins1-2 DC 12 V *17 At least one more indoor units "Operation"
Ch2 0 V Normal
Pins3-4 DC 12 V *17 Error
1
2
3
4
P.C . B
CN410
(Black)
Connected load
*18
connected unit
Connected load
*18
DC power supply
12 V
+
+
+
+
-
-
-
-
*19
*17: Provide a DC 12 V power supply. Select
a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 12 V
across pins 1-2, and 3-4
*18: The allowable current is DC15mA or
less. Provide a load resistance such that the
current becomes DC 15 mA or less.
*19: Polarity is [+] for pins 1,3 and [-] for pins
2,4.
OPERATION STATUS (External output1)
The output for CN410(1-2) is ON when at least one more indoor units is operating.
The output is OFF when all of indoor units is stopped.
CN410(1-2)
Output
Indoor
units
Operation
Stop
12 V
0 V
ERROR STATUS (External output2)
The output for CN410(3-4) is ON when Error of at least one more indoor unit or outdoor unit or
Touch panel controller is generated.
CN410(3 - 4)
Output
Indoor unit or
Outdoor unit
or Touch panel
controller
Error
Normal
12 V
0 V
1-4-3. PARTS
Name and shapes Q'ty Model
EXTERNAL
CONNECT KIT
1 UTY-XWZXZA
- (08 - 63) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT