Design Technical Manual

Table Of Contents
SELECTING THE FUNCTION
The function of the external input terminals is disabled at the factory.
Select the function to be used (following table) by installer setting of application.
* Turn on the power and select by installer setting after starting the application.
Emergency stop
Edge / Pulse
All on / All off
Electricity meter Pulse
INPUT SIGNAL TYPE
The input signal type can be selected.
Edge
L
H
Emergency stop or
All on
CH1
L
H
Emergency stop reset or
All off
Pulse
L
H
300ms or more
Emergency stop or
All on
CH1
Emergency stop reset or
All off
CH2
L
H
50ms or more
Electricity meter signal CH1
H: Energized state L: Shutoff state
When Edge was selected, only CH1 can be used. CH2 cannot be used.
- (08 - 61) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT