Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
EXTERNAL HEATER OUTPUT
(External output4)
Control Primary heater Auxiliary heater
Installation
congration
Function Setting
Indoor unit Wired R. C. Outdoor unit
Control
switching
external
heaters
No.61
IU fan setting for
external heater
DIP-SW2-3
Sensor activation
(UT Y-RNRU, UTY-
RNRUZ*, UTY-
RSRY, UT Y- RH RY,
or UT Y-RNKU)
Presence of heater
selection control
using outdoor unit
sensor No.35
Auxiliary heater
control 1
VRF Heat Pump External device
In-line
61-00
ON (Enable) - -
Individual OFF - -
Auxiliary heater
control 2
VRF Heat Pump External device
In-line
61-01
ON (Enable) - -
Individual OFF - -
Heat pump
prohibition
control
External device None
In-line
61-02
ON (Enable) - -
Individual OFF ON (Enable) *1 -
Auxiliary
heater control
by outdoor
temperature 1
VRF Heat Pump
External device
*2
In-line
61-03
ON (Enable) -
35-01 (Enable)
Individual OFF ON (Enable) *1
Auxiliary heater
selection
control by
outdoor
temperature 2
VRF Heat Pump External device
In-line
61-04
ON (Enable) -
35-01 (Enable)
Individual OFF ON (Enable) *1
Auxiliary heater
selection
control by
outdoor
temperature 3
VRF Heat Pump
External device
*2
In-line
61-05
ON (Enable) -
35-01 (Enable)
Individual OFF ON (Enable) *1
Auxiliary heat
pump control
External device VRF Heat Pump
In-line
61-06
ON (Enable) - -
Individual OFF ON (Enable) *1 -
Auxiliary heat
pump control
by outdoor
temperature 1
External device
VRF Heat Pump
*3
In-line
61-07
ON (Enable) -
35-01 (Enable)
Individual OFF ON (Enable) *1
NOTES :
● Corresponding indoor units: Except wall mounted type.
● After turning off the heater, 3 minutes of standby time is required by next power-on of the heater.
● For items marked "-" in the table, any of validate or invalidate of the setting are acceptable.
● For shaded items in the table, setting change from the factory setting is required.
¾
1: Indoor unit fan setting will be ON for safety reason without sensor activation of Wired R.C.
¾
2: Heating operation is not performed when the outdoor temperature exceeds the boundary specied in
function number 37 setting.
¾
3: Heating operation is not performed when the outdoor temperature is lower than the boundary specied
in function number 36 setting.