Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
FORCED THERMOSTAT OFF FUNCTION
Function setting Mode External input Input signal * Command
60-00, 02, 05, 06, 08 0, 2, 5, 6, 8
CNA03 or CNA04
(EX T.IN2)
OFF → ON EEV OFF
ON → OFF Normal operation
*Edge input only
Example of cooling mode
CNA03 or
CNA04
EEV
Room temp.
Set temp.
On
On
Off
Off
NOTE :
● When the signal is received from another unit on the refrigerant circuit, there may be a
delay in thermostat off function at the unit.
z
Example 1
- In - line connection
- Function setting for Fan setting when cooling thermostat OFF
Number 49-00 (Follow the setting on the remote controller)
Forced thermostat off is one of the function to save energy. For example, case of outdoor
temperature is lower than Indoor temperature, Indoor unit of air conditioner worked as Fan
operation based upon receiving signal from external controller. (Cooling Only)
82˚F
(28˚C)
88˚F
(31˚C)
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Auto
Cool
Heat
Office
Set Temp.
Mode
MenuStatus
Vacation
Fan
Fri 10:00AM
Room Temp.
Cool
Heat
82˚F
(28˚C)
75˚F
(24˚C)
76°F
80°F
74°F
84°F
68°F
Away
Custom
Auto
Cool
Heat
Office
Set Temp.
Mode
Status
Vacation
Room Temp.
Cool
Heat
Cooling operation
(Thermostat on)
Fan operation
(Thermostat off)
External controller
Thermistor
Thermistor
Thermistor
Thermistor
Damper
Indoor
Temperature
Indoor
Temperature
Outdoor
Temperature
Outdoor
Temperature
- (08 - 18) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT