Design Technical Manual

Table Of Contents
Considerations when setting forced stop
CAUTION
When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
Example 1 : OK
Input device 1
Input device 2
Load
resistance
Load
resistance
DC power
supply 12 - 24 V
connected unit
Wired R.C. or
Simple R.C.
Remote controller group
P.C . B
P.C . B
P.C . B
CNA
01
CNA
01
CNA
01
Example 2 : Prohibited
Input device 1
Input device 2
Load
resistance
Load
resistance
DC power
supply 12 - 24 V
connected unit
Wired R.C. or
Simple R.C.
Remote controller group
P.C . B
P.C . B
P.C . B
CNA
01
CNA
01
CNA
01
- (08 - 17) -
EXTERNAL INPUT
& OUTPUT
EXTERNAL INPUT
& OUTPUT