Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
z
SET3-1: Two-stage setting
Cooling setting temperature
(
u
...Factory setting)
SW
SET3-2
Cooling stage 1 setting
Temperature °F (°C)
Cooling stage 2 setting
Temperature °F (°C)
Remarks
u
OFF 68 (20) 64 (18) Pattern 1
ON 72 (22) 68 (20) Pattern 2
Heating setting temperature
(
u
...Factory setting)
SW
SET3-3
SW
SET3-4
Cooling stage 1 setting
Temperature °F (°C)
Cooling stage 2 setting
Temperature °F (°C)
Remarks
u
OFF OFF 81 (27) 86 (30) Pattern 1
OFF ON 77 (25) 82 (28) Pattern 2
ON OFF 75 (24) 79 (26) Pattern 3
ON ON 70 (21) 75 (24) Pattern 4
NOTES:
● Setting values are the limit temperature for cooling and heating.
● Energy saving performance is improved in the order from Cooling Pattern 1 to 2 and Heating pattern 1 to 4.
Delay OFF setting (SET2)
Delay OFF is the function to operate continuously even after reaching to the set temperature of
thermostat. This function may make air conditioning ecient.
Set the Delay OFF time by SW SET2-3 and SW SET2-4.
(
u
...Factory setting)
SW
SET2-3
SW
SET2-4
Delay o time
u
OFF OFF 0 minute
OFF ON 5 minutes
ON OFF 10 minutes
ON ON 20 minutes
Fun setting (Signal on terminal G) (SET2)
(
u
...Factory setting)
SW
SET2-1
SW
SET2-2
Indoor unit airow
u
OFF OFF AUTO
OFF ON HIGH
ON OFF MED
ON ON LOW