Design Technical Manual

Table Of Contents
2-13. CENTRAL REMOTE CONTROLLER
ADDRESS SETTING
Display the Installer Setting screen and Press the [ ] button and move the cursor to
"Central Controller Address Setting".
Press the [ ] button.
Central remote controller address setting
Press the [UP] button or [Down] button.
Set the Address value.
The Address value can be set from 00 to 15.
When the [ ] button is pressed, setting is complete.
NOTES:
Address No. can be set between "00" and "15". (Up to maximum 16 Central Remote
Controller can be installed to 1 system).
When installing two or more Central Remote Controller, set up so that Address No.
does not overlap.
Refer to the OPERATING MANUAL of Central Remote Controller for details.
Keep Address No. of Central Remote Controller from overlapping the controller (Touch
Panel Controller and Network Convertor for L
ON
W
ORKS
®
) connected to the same VRF
Network system
- (07 - 133) -
FUNCTION
SETTING
FUNCTION
SETTING