Design Technical Manual

Table Of Contents
Temperature conditions when the external heater is ON/OFF
Temperature (t) = Room temperature - set temperature
Set value of function: 61
00 01 to 09
ON OFF ON OFF
Set value of function: 62
00
t ˂ -5.4°F (-3°C) t ≥ -1.8°F (-1°C) t ≤ -0.9°F (-0.5°C) t ≥ 0.9°F (+0.5°C)
01
t ˂ -3.6°F (-2°C) t ≥ -1.8°F (-1°C) t ≤ -1.8°F (-1°C) t ≥ 0.9°F (+0.5°C)
02
t ˂ -3.6°F (-2°C) t ≥ -1.8°F (-1°C) t ≤ -3.6°F (-2°C) t ≥ 0.9°F (+0.5°C)
03
t ˂ -5.4°F (-3°C) t ≥ -1.8°F (-1°C) t ≤ -5.4°F (-3°C) t ≥ 0.9°F (+0.5°C)
04
t ˂ -7.2°F (-4°C) t ≥ -1.8°F (-1°C) t ≤ -7.2°F (-4°C) t ≥ 0.9°F (+0.5°C)
05
t ˂ -9.0°F (-5°C) t ≥ -1.8°F (-1°C) t < -9.0°F (-5°C) t ≥ 0.9°F (+0.5°C)
06
t ˂ -5.4°F (-3°C) t ≥ -0.9°F (-0.5°C) t ≤ -0.9°F (-0.5°C) t ≥ 0°F (0°C)
07
t ˂ -3.6°F (-2°C) t ≥ -0.9°F (-0.5°C) t ≤ -1.8°F (-1°C) t ≥ 0°F (0°C)
08
t ˂ -3.6°F (-2°C) t ≥ -0.9°F (-0.5°C) t ≤ -3.6°F (-2°C) t ≥ 0°F (0°C)
09
t ˂ -5.4°F (-3°C) t ≥ -0.9°F (-0.5°C) t ≤ -5.4°F (-3°C) t ≥ 0°F (0°C)
10
t ˂ -7.2°F (-4°C) t ≥ -0.9°F (-0.5°C) t ≤ -7.2°F (-4°C) t ≥ 0°F (0°C)
11
t ˂ -9.0°F (-5°C) t ≥ -0.9°F (-0.5°C) t < -9.0°F (-5°C) t ≥ 0°F (0°C)
12
t ˂ -5.4°F (-3°C) t ≥ -0°F (-0°C) t ≤ -0.9°F (-0.5°C) t ≥ -0.9°F (-0.5°C)
13
t ˂ -3.6°F (-2°C) t ≥ -0°F (-0°C) t ≤ -1.8°F (-1°C) t ≥ -0.9°F (-0.5°C)
14
t ˂ -3.6°F (-2°C) t ≥ -0°F (-0°C) t ≤ -3.6°F (-2°C) t ≥ -0.9°F (-0.5°C)
15
t ˂ -5.4°F (-3°C) t ≥ -0°F (-0°C) t ≤ -5.4°F (-3°C) t ≥ -0.9°F (-0.5°C)
16
t ˂ -7.2°F (-4°C) t ≥ -0°F (-0°C) t ≤ -7.2°F (-4°C) t ≥ -0.9°F (-0.5°C)
17
t ˂ -9.0°F (-5°C) t ≥ -F (-0°C) t < -9.0°F (-5°C) t ≥ -0.9°F (-0.5°C)
- (07 - 124) -
FUNCTION
SETTING
FUNCTION
SETTING