Design Technical Manual

Table Of Contents
Function
Function
number
Setting number Default Details
*1 Deadband
value
69
00
0°C
Choose the minimum temperature between cooling and heating
settings (deadband) for Dual setpoint auto mode (set in No. 68).
01
0.5°C
02
1.0°C
03
1.C
04
2.0°C
05
2.5°C
06
3.0°C
07
3.5°C
08
4.0°C
09
4.5°C
Standby time
for auxiliary
equipment
operation
71
00
Disable
Sets the standby time until the auxiliary equipment operation starts
during primary equipment operation.
For details, refer Chapter 8.
1-2-2. EXTERNAL OUTPUT.
01
1 minute
02
2 minutes
98
98 minutes
99
99 minutes
Emergency heat
73
00
Disable
Enables or disable of emergency heat input
01
Enable
Fan delay time
74
00
1 minute
Sets the fan delay time when the heater is turned o󰀨.
01
50 seconds
02
40 seconds
03
30 seconds
*2 External
heater use in
defrosting
75
00
Disable
Enables or disables the external heater use in defrosting.
01
Enable
*1: Function number 68 and 69 will be usable provided that the corresponding operating device is connected.
*2: When using function number 75, inappropriate heater selection may cause cold air in defrosting.
- (07 - 123) -
FUNCTION
SETTING