Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
Function
Function
number
Setting number Default Details
Control
switching of
external heaters
61
00
Auxiliary heater
control 1
Sets the control method for the external heater being used. For details
of the control method, refer Chapter 8.
1-2-2. EXTERNAL OUTPUT
(heater: external heater, heat pump: VRF outdoor unit).
01
Auxiliary heater
control 2
02
Heat pump
prohibition control
03
Auxiliary heater
control by outdoor
temperature 1
04
Auxiliary heater
control by outdoor
temperature 2
05
Auxiliary heater
control by outdoor
temperature 3
06
Auxiliary heat pump
control
07
Auxiliary heat pump
control by outdoor
temperature 1
08
Auxiliary heat pump
control by outdoor
temperature 2
09
Auxiliary heat pump
control by outdoor
temperature 3
Operating
temperature
switching of
external heaters
62
00
Setting 0
Sets the temperature conditions when the external heater is ON.
For the temperature conditions, see "Temperature conditions when the
external heater is ON".
01
Setting 1
02
Setting 2
03
Setting 3
04
Setting 4
05
Setting 5
06
Setting 6
07
Setting 7
08
Setting 8
09
Setting 9
10
Setting 10
11
Set ting 11
12
Setting 12
13
Setting 13
14
Setting 14
15
Setting 15
16
Setting 16
17
Setting 17
Auto mode
type*
68
00
Single
setpoint
auto
mode
(traditional)
Switches the setting method of auto mode to single or dual (cooling/
heating).
For heat pump systems, it is necessary to set the master indoor unit (by
wired remote controller).
01
Dual setpoint
auto
mode
*: Function number 68 and 69 will be usable provided that the corresponding operating device is connected.
- (07 - 122) -
FUNCTION
SETTING
FUNCTION
SETTING