Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
Function
Function
number
Setting number Default Details
*1 Auto
restart
40
00
Enable
Enables or disables automatic system restart after a power outage.
01
Disable
Cool Air
Prevention
43
00
Super low
Restrains the cold airow with making the airow lower when starting
heating operation. To correspond to the ventilation, set to 01.
01
Follow the setting
on the remote
controller
External
control
46
00
Start/Stop
Allows an external controller to start or stop the system, or to perform
an emergency stop, or to perform a forced stop.
* If an emergency stop is performed from an external controller, same
refrigerant system will be disabled.
* If forced stop is set,indoor unit stops by the input to the external input
terminals,and Start/Stop by a remote controller is restricted.
01
Emergency stop
02
Forced stop
Error
report
target
47
00
All
Changes the target for reporting errors. Errors can either be reported
in all locations, or only on the wired remote.
01
Display only on
central remote
control
Fan setting
when cooling
thermostat OFF
49
00
Follow the setting
on the remote
controller
When set 00, Indoor unit is continued operation based upon Central
remote controller or individual controller set.
Once indoor unit received signal from External controller, Indoor unit
changed Fan mode forcibly.
When set 01, Indoor unit is continued operation based upon Central
remote controller or individual controller set.
Once indoor unit received signal from External controller, Indoor unit
stop forcibly.
Connection of the wired remote controller
(2-wire type or 3-wire type) and switching its thermistor are necessary.
01
Stop
*2 Switching
functions
for external
inputs and
external outputs
terminals
60
00
Mode 0
Set this function when connected to external devices such as the VRF
system ventilator, economizer, humidier, etc.
The connection terminal functions can be changed depending on
the type of external device. For details of the connection terminal
functions, refer to Chapter 8. 1-2. INDOOR UNIT.
01
Mode 1
02
Mode 2
03
Mode 3
04
Mode 4
05
Mode 5
06
Mode 6
07
Mode 7
08
Mode 8
*1 : Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2 : Inappropriate setting may cause an external device malfunction. Conrm whether all the settings have been
performed appropriately according to the installing condition.
- (07 - 121) -
FUNCTION
SETTING
FUNCTION
SETTING