Design Technical Manual

Table Of Contents
13) Press the “
” button to return to the 2-wire remote controller address selection screen
of (2). If setting has been completed, press the FAN ” button to return to the Menu 2-F1
item selection screen.
NOTE:
This item cannot be set from slave remote controllers.
FUNCTION DETAILS
Refer to 2-8. FUNCTION DETAILS.
COMPLETION OF FUNCTION SETTING MODE
15) Press and hold the FAN button for at least 2 seconds to return to the Menu 1 item
selection screen. Then, press and hold the SET TEMP. “ and FAN button for at least
2 seconds at the same time to return to the “Monitor Mode” screen.
SETTING UP EACH INDOOR UNIT
0001 0101 0201 1301 1401 15010 1 2 0 1 0
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Repeat the procedures in steps 1) through 8), and set up the indoor units
requiring function setting.
Simple remote
controller
Simple remote
controller
Simple remote
controller
RESET THE POWER AFTER SETTING UP FUNCTION OF ALL
INDOOR UNITS
Important
¾
If the reset is not performed, function cannot be read in normally.
¾
After all the functions have been set, the circuit breaker needs to be switched o󰀨
for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
¾
The set function is stored in the PCB and will remain in memory even when the
power is turned o󰀨.
However setting function is e󰀨ective after power reset.
Record the function set in the indoor unit on a label, etc., and a󰀩x the label to the
unit so it can be used for after-sales service operations.
- (07 - 115) -
FUNCTION
SETTING
FUNCTION
SETTING