Design Technical Manual

Table Of Contents
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
7 0
Electricity meter
No. setting 1
*2
0 0 Setting number x00
l
¡ ¡
Set the ones digit and tens digit
of the No. of the electricity meter
connected to CN135.
0 1 Setting number x01
9 8 Setting number x98
9 9 Setting number x99
7 1
Electricity meter
No. setting 2
*2"
0 0 Setting number 0xx
l
¡ ¡
Set the hundreds digit of the
No. of the electricity meter
connected to CN135.
0 1 Setting number 1xx
0 2 Setting number 2xx
7 2
Electricity meter
pulse setting 1
*3"
0 0 Setting number xx00
l
¡ ¡
Set the ones digit and tens
digit of the No. of the electricity
meter pulse setting connected
to CN135.
0 1 Setting number xx01
9 8 Setting number xx98
9 9 Setting number xx99
7 3
Electricity meter
pulse setting 2
*3"
0 0 Setting number 00xx
l
¡ ¡
Set the hundreds digit and
thousands digit of the electricity
meter pulse setting connected
to CN135.
0 1 Setting number 01xx
9 8 Setting number 98xx
9 9 Setting number 99xx
*2: When electricity meter No. is set to “000” and “201 to 299, the pulses input to CN135 become ine󰀨ective.
Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135 become ine󰀨ective.
Available setting number is "0001" to "9999"
- (07 - 75) -