Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
2 5 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
2 6 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
2 7 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
2 8
Change of unit
(Temperature)
0 0 Celsius (°C)
l
¡ ¡
0 1 Fahrenheit (°F)
2 9
Change of unit
(Pressure)
0 0 MPa
l
¡ ¡
0 1 psi
3 0
Energy saving
level setting
0 0 Level 1 (stop)
l
¡
-
*1
The capacity limit can be
selected by the external
input terminal (CN133) when
operating with the “Energy
Saving Peak Cut function.”
The lower the level, the more
the eect of energy saving, but
the cooling/heating performance
will also drop.
0 1
Level 2 (operated at
40% capacity)
0 2
Level 3 (operated at
60% capacity)
0 3
Level 4 (operated at
80% capacity)
0 4
Level 5 (operated at
100% capacity)
3 2 Prohibited
0 0 Prohibited
l
Setting prohibited0 1 Prohibited
0 2 Prohibited
3 3 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
3 5
Presence of
heater selection
control using
outdoor
temperature
0 0 No
l
¡
*1
0 1 Yes
3 6
Outdoor
temperature
zone boundary
temperature A
0 0 -4.0 °F (-20 °C)
l
¡
*1
0 1 -0.4 °F (-18 °C)
0 2 3.2 °F (-16 °C)
0 3 6.8 °F (-14 °C)
0 4 10.4 °F (-12 °C)
0 5 14.0 °F (-10 °C)
0 6 17.6 °F (-8 °C)
0 7 21.2 °F (-6 °C)
0 8 24.8 °F (-4 °C)
*1: Do not set this for outdoor units with Slave setting.
- (07 - 73) -
FUNCTION
SETTING
FUNCTION
SETTING