Design Technical Manual

Table Of Contents
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
2 5 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
0 2 Prohibited
0 3 Prohibited
2 6 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
2 7 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
2 8
Change of unit
(Temperature)
0 0 Celsius (°C)
l
¡ ¡
0 1 Fahrenheit (°F)
2 9
Change of unit
(Pressure)
0 0 MPa
l
¡ ¡
0 1 psi
3 0
Energy saving
level setting
0 0 Level 1 (stop)
l
¡
-
*1
The capacity limit can be
selected by the external
input terminal (CN133) when
operating with the “Energy
Saving Peak Cut function.
The lower the level, the more
the e󰀨ect of energy saving, but
the cooling/heating performance
will also drop.
0 1
Level 2 (operated at
40% capacity)
0 2
Level 3 (operated at
60% capacity)
0 3
Level 4 (operated at
80% capacity)
0 4
Level 5 (operated at
100% capacity)
3 2 Prohibited
0 0 Prohibited
l
Setting prohibited0 1 Prohibited
0 2 Prohibited
3 3 Prohibited
0 0 Prohibited
l
Setting prohibited
0 1 Prohibited
3 5
Presence of
heater selection
control using
outdoor
temperature
0 0 No
l
¡
*1
0 1 Yes
3 6
Outdoor
temperature
zone boundary
temperature A
0 0 -4.0 °F (-20 °C)
l
¡
*1
0 1 -0.4 °F (-18 °C)
0 2 3.2 °F (-16 °C)
0 3 6.8 °F (-14 °C)
0 4 10.4 °F (-12 °C)
0 5 14.0 °F (-10 °C)
0 6 17.6 °F (-8 °C)
0 7 21.2 °F (-6 °C)
0 8 24.8 °F (-4 °C)
*1: Do not set this for outdoor units with Slave setting.
- (07 - 73) -
FUNCTION
SETTING
FUNCTION
SETTING