Design Technical Manual

Table Of Contents
LED105
CODE No.
Setting Mode
LED104
CODE No.
Setting Function
Factory
setting
Outdoor unit
Remarks
Master Slave
4 0
Capacity
priority setting
(in low noise
mode)
0 0 O󰀨 (quiet priority)
l
¡
-
*1
If the cooling/heating
performance becomes
insu󰀩cient when the low noise
mode is set, it is possible to
set “capacity priority” that
automatically cancels the low
noise mode (once performance
is restored, the mode will
automatically return to the low
noise mode).
0 1 On (capacity priority)
4 1
Low noise
mode setting
0 0 O󰀨 (Normal)
l
¡
-
*1
0 1 On (Low noise mode)
4 2
Low noise
mode
operation level
setting
0 0 Level 1
l
¡
-
*1
Level1: The operating sound
lowers from about 3 to 5 dB(A)
more than the rated value
Level2: The operating sound
lowers from about 3 to 5 dB(A)
more than the Level1
0 1 Level 2
6 0
Back up
operation 1
0 0 On
l
¡
-
*1
0 1 O󰀨
6 1 Prohibited
0 0 On
l
Setting prohibited
0 1 O󰀨
6 2 Prohibited
0 0 On
l
Setting prohibited
0 1 O󰀨
6 3 Prohibited
0 0 On
l
Setting prohibited
0 1 O󰀨
*1: Do not set this for outdoor units with Slave setting.
- (07 - 64) -
FUNCTION
SETTING
FUNCTION
SETTING