Design Technical Manual

Table Of Contents
7) When the number of indoor units appear on the LED104, LED105, press the SELECT button
(SW108), the display changes to volume ratio of the indoor units.
LED105 LED104
LED105 LED104
Ex.) When volume ratio of the indoor units is 120 %.
8) When “the number of indoor units” or “volume ratio of the indoor units connection” appears on
the LED104, LED105, press the ENTER button (SW109). When Indoor Unit Connection Check
is completed, the display changes to “PASS”.
LED105 LED104
LED105 LED104
When Indoor Unit Connection Check is error, the display changes to “Err.” or “number of error
every one second.
LED105 LED104LED105 LED104
Ex.) Shown numbers of error are three.
When conrm the contents of the error , push the ENTER button (SW109). When there are
some errors, display change by push the SELECT button (SW108).
●Number of indoor unit connection is error (5 Ton:1~9, 4 Ton:1~8, 3 Ton:1~6).
Volume ratio of the indoor units connection is error (3, 4, 5 Ton:50~130%).
● Overlap address of the indoor unit is error.
Display the address of the overlap indoor unit, hold down the ENTER button (SW109).
Ex.) Shown that overlap address to indoor unit address 3.
9) To exit the Indoor Unit Connection Check , press the ENTER button (SW109) in the setting
completed status shown in step 8) above.
LED105 LED104
LED105 LED104
Next, press the MODE/EXIT button (SW107) to exit the Function mode.
LED105 LED104
LED105 LED104
LED105 LED104 LED105 LED104
LED105 LED104 LED105 LED104
LED105 LED104 LED105 LED104
LED105 LED104LED105 LED104
- (07 - 57) -
FUNCTION
SETTING
FUNCTION
SETTING