Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
1-5-1. SIGNAL AMPLIFIER AUTOMATIC ADDRESS SETTING
CAUTION
● The Signal Amplifier Automatic Address Setting function can be used for a maximum of 40
signal amplifiers installed within the same network.
● Perform the automatic address setting of signal amplifiers on only one outdoor unit (master
unit) within the same network. (Do not set them again from other outdoor unit.)
● When setting the address of a signal amplifier automatically, be sure to always set the
address on the printed circuit board of the Signal amplifier to “1”(factory setting).
● Perform automatic address setting after checking that filter mode setting of Signal amplifier
is completed.
1) After verifying that the system is normally, press the MODE/EXIT button (SW107) once.
LED105 LED104
LED105 LED104
2) Press the SELECT button (SW108) to display “F3” on the LED104.
(The display of the LED104 changes each time the SELECT button is pressed.)
LED105 LED104LED105 LED104 LED105 LED104 LED105 LED104
*1 *1
(Monitoring mode) (Setting mode) (Function mode)
(Error history mode)
*1 : The “F1” and “F9” modes are used for maintenance, so do not set them in regular
3) When “F3” appears on the LED104, press the ENTER button (SW109).
LED105 LED104
LED105 LED104
A ashing display appears on the LED105.
4) Press the SELECT button (SW108) to display “10” on the LED105.
LED105 LED104
LED105 LED104
5) When “10” appears on the LED105, hold down the ENTER button (SW109) for at least 3
seconds. (Unless it is held down for at least 3 seconds, the selection will not be conrmed.)
LED105 LED104
LED105 LED104
When the Automatic Address Setting function is activated, the display changes to “run.”