Design Technical Manual

Table Of Contents
SWITCHING SELECTION OF ADDRESS SETTING MODE
4) To activate the address setting mode, hold down the three buttons of SET TEMP. V, SET
TEMP. Λ and FAN at the same time for 5 seconds or longer.
Address setting mode initial display
BUTTON NAME AND FUNCTION
Refer to “5-2” for an outline of the address setting.
It does not matter whether the refrigerant circuit address or indoor unit address is set first.
(The method shown here sets the indoor unit address first.)
During address setting mode, indoor unit will not recognize any remote controller operation commands.
Function number
01---Indoor unit address
02---Refrigerant circuit address
Remote controller address
Remote controller address
setting number 00-15
SET BACK button
Switches the remote controller
address setting number.
SET TIME “<” and “>” button
Switches the function number.
Setting number
Setting number
Indoor unit address valid
range 00-63
Refrigerant circuit address
valid range 00-99
SET TEMP. “V” and “
Λ
” button
Switches the setting
number.
TIMER SET button
Transmits address setting
- (07 - 24) -
FUNCTION
SETTING
FUNCTION
SETTING