Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
z
RB unit address (Set P)
Each RB unit in same refrigerant system should be set an exclusive RB unit address.
00 00 00 01 00 020 1 2 00 13 14 1500 000 1 0
00 00 00 01
000
2 3
100
3
200
3
RB unit
address
Rotary SW setting
RB AD x10 RB AD x1
03
0 3
11
1 1
30
3 0
47
4 7
*Setting range 00 - 63(Arbitrary numbers can be set)
*Do not set RB unit address to the range of 64 from 99.
*Do not set the same address number to two or more RB units.
- (07 - 12) -
FUNCTION
SETTING
FUNCTION
SETTING