Design Technical Manual

Table Of Contents
MEDIUM STATIC PRESSURE DUCT TYPE
Attached band
Supporter
Attached drain hose
Downward gradient
1/100 or more
Arrange the drain hose
lower than this position
60. to 79in. (1.5 to 2.0m)
Air bleeding
Rise
Trap
Prohibited
There is a drain port on the left and right sides. Select the drain port to match the local
conditions.
Nylon fastener
Drain port Drain cap
CAUTION
Always check that the drain cap is installed to the unused drain port and is fastened with the nylon
fastener.
If the drain cap is not installed, or is not sufficiently fastened by the nylon fastener, water may drip
during the cooling operation.