Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
z
Step 7
Conrm proper installation of transmission line.
Conrm transmission line connections to indoor units.
Conrm that there is one terminal resistor on each
each network segment.
Measure the resistance of the signal amplier
terminal and the terminal of the indoor and outdoor
units connected farthest away from the device where
terminal resistor is measured.
A value from the table is displayed, depending on
the distance from the signal amplier and the device
where the terminal resistor is set.
This value is an estimate.
●
Always ground both ends of the transmission line.
X1 X2
TRANS-
MISSION
X1 X2
TRANS-
MISSION
Transmission line
Indoor unit Indoor unit
z
Step 8
Conrm total Signal amplier in VRF Network according following rule.
Signal amplier of lter mode OFF ≤ 8 units
Signal amplier of lter mode ON ≤ 32 units
z
Step 9 : Conrm transmission wiring system in VRF network
Conrm transmission wiring is within the following parameters:
Check list
1) Maximum transmission line length between units in 1 segment: Maximum 1312 ft. (400 m)
2) Total transmission line length in 1 segment: Maximum 1640 ft. (500 m)
3) Total transmission line length in 1 VRF network: Maximum 11811 ft. (3600 m)
4) The total number of element in 1 segment: Maximum 64
5) Total of Segment in 1 VRF network: Maximum 9 segments
Distance from termination resistor ft. (m)
Approximate resistance
(Ω)
0 ~ 50
A short circuit somewhere or 2 or
more termination resistors are connected
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190 ~ Faulty contact or wiring length over 1614 (500)
1K ~
∞
Faulty contact, open circuit, or no
termination resistor
(0 ~ 100) ( ~ 200) ( ~ 300) ( ~ 400) ( ~ 500)
0 ~ 328 ~ 656 ~ 984 ~ 1312 ~ 1640
- (06 - 125) -