Design Technical Manual

Table Of Contents
Signal amplier (Filter mode: ON)
Set the Filter mode to suppress an increase of the amount of communication information in the VR-II system.
Filter mode is turned on by inserting the accessory connecting wire at the CN4 connector on the PC board.
When the Filter mode setting is changed, turn the power off once. Otherwise, the setting will not be recognized.
CN4
Signal amplier (Filiter mode: ON)
Signal amplier PCB
Connector
(accessory)
z
Step 5
Conrm wiring lengths are within the following parameters:
1) Total transmission line length. (In 1 segment): MAX 1640 ft. (500 m)
2) Maximum wiring length between units. (In 1 segment): MAX 1312 ft. (400 m)
Note: If wiring length is not meet the rule, install a Signal amplier that is set lter mode OFF.
- (06 - 123) -
SYSTEM
DESIGN
SYSTEM