Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
PATTERN B (Serial connection)
z
Step 1
Follow each step according to Wiring Rule.
1) Maximum transmission line length between units in 1 segment: Maximum 1312 ft. (400 m)
2) Total transmission line length in 1 segment: Maximum 1640 ft. (500 m)
3) Total transmission line length in 1 VRF network: Maximum 11811 ft. (3600 m)
4) The total number of element in 1 segment: Maximum 64
5) Total of Segment in 1 VRF network: Maximum 9 segments
(Before Signal amplier installation)
B A
F
C D E
LKJ
G
I
H
VRF Network
Segment
1
1
1 1
1
1
1
2
2
2 2 3 2
2 2
3 4
70
45
44
46
47
Transmission line
RB unit
RB unit
Segment 1
1) Maximum transmission line length
between units in 1 segment:
BC=328 ft. (100 m) < 1312 ft. (400 m)
→OK
2) Total transmission line length in 1
segment:
● AB+BC+CD+DE+EF = 2296 ft. (700m) >
500m →Prohibited
●CG=32 ft. (10m) < 1640 ft. (500m) →OK
●DH=32 ft. (10m) < 1640 ft. (500m) →OK
●EI=49 ft. (15m) < 1640 ft. (500m) →OK
●FJ=32 ft. (10m) < 1640 ft. (500m) →OK
●FK=32 ft. (10m) < 1640 ft. (500m) →OK
●FL=32 ft. (10m) < 1640 ft. (500m) →OK
3) Total transmission line length in 1 VRF
network: 4921 ft. (1500 m) < 11811 ft.
(3600 m) →OK
4) The total number of element in 1
segment: 70 > 64 →Prohibited
5) Total of Segment in 1 VRF network:
3 segments < 9 segments →OK
(After Signal amplier installation )
B A
F
C D E
L
M
N
KJ
G
I
H
VRF Network
Segment
1
1
1 1
1
1
2
1
1
2
2
2 2 3 2
2 2
3 4
26
45
44
46
3
Transmission line
Segment 2
Segment 1
Signal
Amplier
RB unit
RB unit
1) Maximum transmission line length
between units in 1 segment:
BC=328 ft. (100 m) < 1312 ft. (400 m)
→OK
2) Total transmission line length in 1
segment:
● AB+BC+CD+DE+EM
= 1476 ft. (450m) (Seg 1)< 1640 ft.
(500m) →OK
● NF=820 ft. (250m) (Seg 2)< 1640 ft.
(500m) →OK
●CG=32 ft. (10m) < 1640 ft. (500m) →OK
●DH=32 ft. (10m) < 1640 ft. (500m) →OK
●EI=49 ft. (15m) < 1640 ft. (500m) →OK
●FJ=32 ft. (10m) < 1640 ft. (500m) →OK
●FK=32 ft. (10m) < 1640 ft. (500m) →OK
●FL=32 ft. (10m) < 1640 ft. (500m) →OK
3) Total transmission line length in 1 VRF
network: 4921 ft. (1500 m) < 11811 ft.
(3600 m) →OK
4) The total number of element in 1
segment:
Segment 1: 46 < 64 →OK
Segment 2: 26 < 64 →OK
5) Total of Segment in 1 VRF network:
4 segments < 9 segments →OK