Design Technical Manual

Table Of Contents
z
Step 2
One Terminal resistor should be installed on each segment.
1
2
3 25
26
1
2 24
25
26
50
51
2
1
3 2
1
3
2
1
27 49
3 2
1
3
2
1
3 2
1
3
B A
MN
PO
RQ
C
F
I J LK
G HE
S
T
D
VRF Network
Segment
1
2
3 25
26
RB unit
Terminal
resistor
Terminal
resistor
Segment 1
Segment 2
Seg 1 Seg 2
The 4th switch in SET5 DipSW of
Outdoor unit PCB
(On: Enable, O󰀨: Disable)
Signal amplier PCB
NOTE: It is not necessary to install a terminal resistor between the RB Unit and the indoor unit;
the terminal resistor is built into the RB Unit.
z
Step 3
Conrm proper installation of transmission line.
Conrm transmission line connections to indoor units.
Conrm that there is one terminal resistor on each
each network segment.
Measure the resistance of the signal amplier
terminal and the terminal of the indoor and outdoor
units connected farthest away from the device where
terminal resistor is measured.
A value from the table is displayed, depending on
the distance from the signal amplier and the device
where the terminal resistor is set.
This value is an estimate.
Distance from termination resistor ft. (m)
Approximate resistance
(Ω)
0 ~ 50
A short circuit somewhere or 2 or
more termination resistors are connected
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190 ~ Faulty contact or wiring length over 1614 (500)
1K ~
Faulty contact, open circuit, or no
termination resistor
(0 ~ 100) ( ~ 200) ( ~ 300) ( ~ 400) ( ~ 500)
0 ~ 328 ~ 656 ~ 984 ~ 1312 ~ 1640
- (06 - 112) -