Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
z
How to count Segments between each units
Counting conditions
1) Start counting from a corner of a segment.
2) Counting ends at the segment end.
3) When there are RB unit and Signal amplier, the segment is divided there.
4) The path with the maximum number of segments will be used to determine proper
installation.
●
Example 1
Segment 1
Segment 2
Segment 3
Unit A Unit B
The number of segment in route of between Unit A to Unit B: "3"
Judgement: The maximum number of segment is "3" → OK
●
Example 2
Segment 1
Segment 2 Segment 3
Segment 3-B Segment 4
Unit A Unit B Unit C
The number of segment in route of between Unit A to Unit B: "3"
The number of segment in route of between Unit A to Unit C: "4"
Judgement: The maximum number of segment is "4" → OK
- (06 - 107) -
SYSTEM
DESIGN
SYSTEM