Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
z
Meaning of "Units"
Model name "Units" Count
RB unit UTP-RU01AH
UTP-RU01BH
UTP-RU01CH
1
UTP-RU04BH 4
Indoor unit
(Except High static pressure duct type (72/96 type)
and Vertical air handler type)
AUUA4TLAV1
AUUA7-24TLAV
AUUB18-48TLAV1
AUUB18-36TLAV
ARUL4TLAV1
ARUL7-18TLAV
ARUM24-36TLAV
ARUH36-60TLAV
AGUA4-14TLAV1
ABUA12-36TLAV
ASUA4-14TLAV1
ASUB18-36TLAV1
ASUA7-14TLAV
ASUB18-24TLAV
1
Indoor unit
(High static puressure duct (72/96 type))
ARUH72-96TLAV 3
Indoor unit
(Vertical air handler type)
ARUV12- 60TLAV 4
Example 1)
Connectable indoor unit : ASUA9TLAV x 4 + AUUB18TLAV x 2 + ARUL9TLAV
Amount of "Units" : 1 x 4 + 1 x 2 + 1 x 1 = 7
Example 2)
Connectable indoor unit : ARUH72TLAV1 + AUUB18TLAV x 2 + ARUL9TLAV
Amount of "Units" : 3 x 1 + 1 x 2 + 1 x 1 = 6
Example 3)
Connectable indoor unit : ARUV12TLAV + AUUA9TLAV x 2 + ARUL9TLAV x 2 + UTP-RU01AH x 1
+ UTP-RU04BH x 1
Amount of "Units": 4 x 1 + 1 x 2 + 1 x 2 + 1 x 1 + 4 x 1 = 13
●
Select the power cable type and size in accordance with local regulations.
●
Include at least one breaker and one disconnect per refrigerant system.
●
Power supply circuits should only be connected to units on the same refrigerant circuit.
●
Design the power supply circuit to keep the voltage drop within 2%.
- (06 - 92) -
SYSTEM
DESIGN
SYSTEM
DESIGN