Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
WIRING SYSTEM OUTLINE
Refrigerant system 1
3 Phase 60 hz 208/230V
3 Phase 60 hz 208/230V
3 Phase 60 hz 208/230V
Outdoor unit power supply cable
3N 3W 60Hz 208/230V
Remote controller cable (2 line) non-polar 2 core cable,
seathed cable 22AWG (0.33mm
2
)
*Shilded cable might
be required in accordance with the regional standard
Remote controller cable (2 line) polar
2 core cable, seathed cable 22AWG
(0.33mm
2
)
*Shilded cable might
be required in accordance with the
regional standard
Refrigerant system 2
USB adaptor
(locally purchased)
USB
adaptor
USB
adaptor
USB
adaptor
Central
Remote
Controller
UTY-ABGXZ1
Network
convertor
for
L
ON
W
ORKS
®
UTY-VLGX
Network convertor
UTY-VGGXZ1
Signal Amplier
UTY-VSGXZ1
Web Monitoring Tool
Internet
or
Public Telephone Line
Transmission line
line is non-polar 2-conductor.
Required in case of follows
Transmission line 1640ft. (500m) or more
Number of unit 64 or more
Can be connect anywhere
on transmission line
(Locally purchased)
(Locally purchased)
External switch controller cable
Polar 3 core, shielded, 22AWG (0.33mm
2
)
Max length 82ft. (25m)
Remote controller cable
Polar 3 core, 22AWG (0.33mm
2
)
System without remote controller
Together with Touch panel controller, it is
possible to build non remote controller system.
Remote controller line (2 wire)
Maximum 16 units can be controlled
Total wiring length : Max 1640ft. (500m)
Remote controller line (3 wire)
Maximum 16 units can be controlled
Total wiring length : Max 1640ft. (500m)
Touch Panel
Controller
System
Controller
IR Receiver Kit
Cassette type indoor unit can be
controlled with wireless remote controller
IR receiver unit
Duct type indoor unit
can be controlled with
wireless remote controller.
Service Tool
Card key
Single system
Outdoor unit
Indoor unit
(Cassette)
Indoor unit
(Duct)
RB unit
(Single)
RB unit
(Multi)
Touch Panel
Controller
Wired Remote
Controller
Wired Remote
Controller
Central Remote
Controller
Simple Remote
Controller
Simple Remote
Controller
Simple Remote
Controller
Transmission line
Module link
Remote controller
line (3 wire)
Remote controller
line (2 wire)
Signal line
(single system)
USB cable
Ethernet
L
ON
W
ORKS
®
Network
Wireless Remote
Controller
External Switch
Controller
IR Receiver unit
(VRF system side)
(Monitoring side)
(Monitoring side)
(Monitoring side)
BACnet® Gateway
BACnet®
L
ON
W
ORKS
®
L
ON
W
ORKS
®
Network
BACnet®
BACnet® Operator
Workstation (B-OWS)
NW1
NW2
NW3
NW4
1ø 60Hz 208/230V
1ø 50/60Hz 220-240V
1ø 50/60Hz 220-240V
1ø 50/60Hz 100 to 240V
1ø 50/60Hz 100 to 240V
1ø 60Hz 208/230V
1ø 50/60Hz 220-240V
1ø 50/60Hz 220-240V
Disconnect switch might be required in accordance with the regional standard.
Transmission cable
Non polar 2core,
shielded Level4,
22AWG (0.33mm
2
)
(Remote /
Monitoring
side)
(Remote /
Monitoring
side)
1ø 60Hz 208/230V
- (06 - 90) -
SYSTEM
DESIGN
SYSTEM
DESIGN