Design Technical Manual

Table Of Contents
3-5. RB UNIT
MODELS
RB unit
Maximum number of
connectable indoor units
per branch
Connectable cooling capacity range
Single type
UTP-RU01AH 3 27,000 Btu/h or less
UTP-RU01BH 8 60,000 Btu/h or less
UTP-RU01CH 8 96,000 Btu/h or less
Multi type UTP-RU04BH 8
60,000 Btu/h or less
for 1 branch
191,000 Btu/h or less
(Sum total of 4 branches)
3-5-1. SINGLE TYPE
Gas pipe
Suction gas pipe
Discharge gas pipe
UPWARD
A
B
C
INSTALLATION
Be sure to install so that the top side faces up.
z
Ceiling installation
Wall installation
Unit : in. (mm)
20 (500) or more 20 (500) or more
1 (20) or more
1 (20) or more
Top side
Top side
4 (100)
16 (400)
16 (400)
A C
B
Service access
Control box
service
space
grille
1 (20)
or more
1 (20) or more
12 (300)
or more
E.g.: If installing a duct model vertically.
Top side
- (06 - 79) -
SYSTEM
DESIGN
SYSTEM
DESIGN