BRANCH KIT
Outdoor unit Branch Kit(s) is (are) required for multiple outdoor unit.
Outdoor unit Model Q'ty
2 outdoor units
UTP-DX567A
1
3 outdoor units 2
z
Installation
Make sure to connect outdoor unit branch kit in correct direction.
Outdoor unit1
(Master unit)
To indoor unit
Outdoor unit2
(Slave unit1)
Outdoor unit3
(Slave unit2)
To outdoor unit
or next branch kit
To outdoor unit
To RB unit or indoor unit
(To main pipe)
Outdoor unit
branch kit
(Optional)
Liquid pipe
(Locally
purchased)
Suction gas pipe
(Locally purchased)
Discharge gas pipe
(Locally purchased)
Joint pipe
(Accessory)
L
1/2L 0 to 1/8 in (0 to 3 mm)
Joint pipe (Branch kit)
Joint pipe
(Branch kit)
Connections
Field pipe
Field pipe
Reducer or
Expander
Standard cutting position:
1/2L
+1/8
-0
in. (1/2L
+3
-0
mm)
Use the pipe cutter to cut at the location which matches the piping size when the piping size is
di󰀨erent.
When the pipe size of the branch kit itself does not match, or when piping sizes di󰀨er even if it
cuts the pipe, use attached Reducer or attached Expander.
NOTE: Insert the eld pipe rmly until it touches the joint pipe (Branch kit).
- (06 - 69) -