Design Technical Manual

Table Of Contents
z
Pipe connection
CAUTION
Seal the pipe route hole with putty (locally purchased) such that there are no gaps.
Small insects or animals that are trapped in the outdoor unit may cause a short circuit in the
electrical component box.
To prevent pipe damage; do not make sharp bends.
Bend the pipe at a radius of 2-3/4in. (70mm) or greater.
Do not bent pipe many times at same part to prevent break.
After completing all the pipe connection by brazing, perform the indoor unit pipe connection with a
flare joint.
When removing the pinch pipe or brazing the joint pipe, carry out the work while cooling down the
3-way valve sufficiently.
Braze the joint pipe onto the 3-way valves at the liquid , suction gas and discharge gas side.
Install the joint pipe appropriately so that it can be connected easily with the main pipe.
Braze the joint pipe at the liquid , suction gas and discharge gas side with the main pipe.
* Be sure to supply nitrogen when brazing.
Knockout hole
Knockout hole
Joint pipe A
(Accessories)
Joint pipe D
(Accessory or Locally purchased) *1
Joint pipe B
(Accessory or Locally purchased) *1
*1) Locally purchased and accessory
depend on the model, so for details,
refer to "accessories of outdoor unit".
Joint pipe C
(Accessories)
Joint pipe
(Locally
purchased)
Joint pipe
(Locally
purchased)
Suction gas pipe
(Locally purchased)
Discharge gas pipe
(Locally purchased)
Liquid pipe (Locally
purchased)
To RB unit or indoor unit
- (06 - 68) -