Design Technical Manual
Table Of Contents
- CHAPTER00
- CHAPTER01_General_information
- CHAPTER02_Model_selection
- 1. MODEL SELECTION PROCEDURE
- 2. MODEL LINE UP
- 3. MODEL SELECTION AND CAPACITY CALCULATION
- 4. CAPACITY TABLE COOLING (OUTDOOR UNIT)
- 5. CAPACITY TABLE HEATING (OUTDOOR UNIT)
- 6. CAPACITY COMPENSATION COEFFICIENT
- 7. CAPACITY TABLE COOLING (INDOOR UNIT)
- 7-1. COMPACT CASSETTE TYPE
- 7-2. CIRCULAR FLOW CASSETTE TYPE
- 7-3. CASSETTE TYPE
- 7-4. MINI DUCT TYPE
- 7-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 7-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 7-7. HIGH STATIC PRESSURE DUCT TYPE
- 7-8. VERTICAL AIR HANDLER TYPE
- 7-9. COMPACT FLOOR TYPE
- 7-10. FLOOR / CEILING TYPE
- 7-11. CEILING TYPE
- 7-12. WALL MOUNTED TYPE
- 8. CAPACITY TABLE HEATING (INDOOR UNIT)
- 8-1. COMPACT CASSETTE TYPE
- 8-2. CIRCULAR FLOW CASSETTE TYPE
- 8-3. CASSETTE TYPE
- 8-4. MINI DUCT TYPE
- 8-5. SLIM DUCT / SLIM CONCEALED FLOOR TYPE
- 8-6. MEDIUM STATIC PRESSURE DUCT TYPE
- 8-7. HIGH STATIC PRESSURE DUCT TYPE
- 8-8. VERTICAL AIR HANDLER TYPE
- 8-9. COMPACT FLOOR TYPE
- 8-10. FLOOR / CEILING TYPE
- 8-11. CEILING TYPE
- 8-12. WALL MOUNTED TYPE
- CHAPTER03_Outdoor_units
- CHAPTER04_Indoor_units
- CHAPTER05_Control_system
- 1. CONTROL SYSTEM
- 2. CONTROL UNITS
- 2-1. SYSTEM CONTROLLER
- 2-2. SYSTEM CONTROLLER LITE
- 2-3. TOUCH PANEL CONTROLLER
- 2-4. CENTRAL REMOTE CONTROLLER
- 2-5. WIRED REMOTE CONTROLLER (Touch panel)
- 2-6. WIRED REMOTE CONTROLLER
- 2-7. SIMPLE REMOTE CONTROLLER (With Operation mode)
- 2-8. SIMPLE REMOTE CONTROLLER (Without Operation mode)
- 2-9. WIRELESS REMOTE CONTROLLER
- 2-10. IR RECEIVER UNIT (for ALL DUCT TYPE)
- 2-11. IR RECEIVER UNIT (for CASSETTE TYPE)
- 2-12. IR RECEIVER UNIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-13. HUMAN SENSOR KIT (for CIRCULAR FLOW CASSETTE TYPE)
- 2-14. REMOTE SENSOR UNIT
- 2-15. PRESSURE SENSOR KIT
- 2-16. GROUP CONTROL METHOD
- 2-17. COMPARISON TABLE OF CONTROLLERS
- 3. ADAPTOR / CONVERTOR UNITS
- 4. SERVICE & WEB MONITORING TOOL
- CHAPTER06_System_design
- CHAPTER07_Function_setting
- CHAPTER08_External_input_and_output
- CHAPTER09_Notes
- CHAPTER10_Optional_parts
- CHAPTER99
z
Selection of branch kit
Branch kit
No.
Total cooling
capacity of
downstream indoor
units (kBtu/h)
Model
DX1 - UTP-DX567A
DX2 - UTP-DX567A
BX1
348.0
UTP-BX567A
AX1
355.5
UTP-A X567A
AX2
264.0
UTP-A X567A
AX3
240.0
UTP-A X567A
AX4
84.0
UTP-AX090A
AX5
24.0
UTP-AX090A
HD1
192.0
UTP-J1806A
z
Selection of RB unit
RB unit
No.
Total cooling
capacity of
downstream indoor
units (kBtu/h)
Model
RB1 48.0 UTP-RU01BH
RB2 48.0 UTP-RU01BH
RB3 48.0 UTP-RU01BH
RB4 48.0 UTP-RU01BH
z
Selection of pipe size
1) 3pipes
3a 3b 3c 3d 3e 3f 3g 3h 3i 3j
Liquid pipe
in. (mm)
1/2
(12.70)
1/2
(12.70)
1/2
(12.70)
5/8
(15.88)
3/4
(19.05)
3/4
(19.05)
5/8
(15.88)
5/8
(15.88)
5/8
(15.88)
1/2
(12.70)
Discharge
gas pipe
in. (mm)
3/4
(19.05)
3/4
(19.05)
3/4
(19.05)
7/8
(22.22)
1-1/8
(28.58)→
7/8
(*2)
(22.22)
1-1/8
(28.58)→
7/8
(*2)
(22.22)
1-1/8
(28.58)→
3/4
(*2)
(
19.05)
1-1/8
(28.58)→
3/4
(*2)
(
19.05)
7/8
(22.22)→
3/4
(*2)
(
19.05)
3/4
19.05→
1/2
(*2)
(12.70)
Suction gas
pipe
in. (mm)
7/8
(22.22)
7/8
(22.22)
7/8
(22.22)
1-1/8
(28.58)
1-3/8
(34.92)
1-5/8
(41.27)
→
1-3/8
(*1)
(34.92)
1-3/8
(34.92)
1-3/8
(34.92)
1-1/8
(28.58)
7/8
(22.22)
Length ft. (m)
Example
6
(2)
6
(2)
6
(2)
6
(2)
164
(50)
33
(10)
33
(10)
16
(5)
16
(5)
16
(5)
3k 3l 3m 3n
Liquid pipe
in. (mm)
3/8
(9.52)
3/8
(9.52)
3/8
(9.52)
3/8
(9.52)
Discharge
gas pipe
in. (mm)
1/2
(12.70)
1/2
(12.70)
1/2
(12.70)
1/2
(12.70)
Suction gas
pipe
in. (mm)
3/4
(19.05)
3/4
(19.05)
3/4
(19.05)
3/4
(19.05)
Length ft. (m)
Example
10
(3)
10
(3)
10
(3)
10
(3)
*1: Pipe size "3f" selection : Even though this pipe size might be selected based on downstream
cooling capacity (348.0kBtu/h), This pipe size should not be larger than pipe size "3e". Therefore
select pipe size equal to pipe size "3e".
*2: Discharge gas pipe size selection :
When indoor unit of cooling only type is connected, it calculates with the value except
capacity of cooling only type. (except pipe size "3e")
Pipe diameter, in case of discharge gas pipe is not separated, is dierent between pipes
which come from outdoor unit side and connected to RB unit, Thinner piping diameter should
be selected.
Model Q'ty
UTP-DX567A 2
UTP-BX567A 1
UTP-A X567A 3
UTP-AX090A 2
UTP-J1806A 1
Model Q'ty
UTP-RU01BH 4
- (06 - 58) -
SYSTEM
DESIGN
SYSTEM