Design Technical Manual

Table Of Contents
Model
Maximum
connectable
units in one VRF
network system
Remarks
Adaptor / Convertor
Signal
Amplier
UT Y-VSGXZ1 40
The signal amplier is required when
1640ft. (500m) or more in transmission
line length or connected unit exceeds
64units.
Network
Convertor
UT Y-VTGX
Used for
connecting split
system : 100
Total number
of refrigerant
system and
Network
convertor is
maximum 100.
Max connectable Single split type or
Multi type : 16 units.
UTY-VGGXZ1
Max connectable Single split or Multi
system in a UTY-VGGXZ1 : 16 units.
Network
Convertor for
L
ON
W
ORKS
®
UT Y-VLGX 1
*2:Note
Max controllable indoor units : 128
Modbus
®
Convertor for
VRF
UT Y-VMGX 9
BACnet
®
Gateway
(Hardware)
UT Y-VBGX 4
BACnet
®
Gateway
(Software)
UT Y-ABGXZ1 1
*1:Note
Max.controllable VRF network system : 4
Max.controllable remote controller
groups : 1600 per 4 VRF network system
Max.controllable indoor unit : 1600 per 4
VRF network system
Max.controllable groups : 1600 per 4
VRF network system
External
Switch
Controller
UT Y-TERX
UT Y-TEKX
Max connectable indoor units : 16
Service & Maintenance
Service Tool UTY-ASGXZ1
1
1 Service
Tool or 1 Web
Monitoring
Tool can be
connected.
PC : Locally purchased
USB adaptor is required.
Web
Monitoring
Tool
UT Y-AMGX Z1
*1:Note
.
Web Monitoring Tool: Internet explorer
6.0 or higher.
PC : Locally purchased
Up to 4 VRF network system can be
observed with one Web Monitoring Tool.
*1 Note: Di󰀨erent VRF series may be connected for each of the 4 VRF networks supported by the
unit, but di󰀨erent series may not coexist within the same network.
(VR-II Series and V-II Series Series can exist together on same network.)
*2 Note : For one VRF network system, total number of Touch Panel Controller, Central Remote
Controller, Network Convertor for Group Remote Controller, Modbus
®
Convertor for VRF,
BACnet
®
Gateway (Hardware) is 16, including one Network Convertor for L
ON
W
ORKS
®
.
- (06 - 28) -
SYSTEM
DESIGN