Design Technical Manual

Table Of Contents
CONTROLLER AND CONVERTOR
Model
Maximum
connectable
units in one VRF
network system
Remarks
Controller
Central Control
System
Controller
UT Y-APGXZ1 1
*1:Note
Max.controllable VRF network system : 4
Max.controllable remote controller
groups : 1600 per 4 VRF network system
Max.controllable indoor unit : 1600 per 4
VRF network system
Max.controllable groups : 1600 per 4
VRF network system
System
Controller Lite
UT Y-ALGXZ1 1
Max.controllable VRF network system : 1
Max.controllable remote controller
groups : 400
Max.controllable indoor unit : 400
Max.controllable groups : 400
Touch Panel
Controller
UT Y-DTGYZ1 16
*2:Note
Max.controllable remote controller
groups : 400
Max.controllable indoor unit : 400
Max.controllable groups : 400
Central
Remote
Controller
UT Y-DCGY 16
Max.controllable indoor unit : 100
Max.controllable groups : 16
Individual Control
Wired Remote
Controller
UT Y-RNRUZ2 Max controllable indoor units : 16
UT Y-RNKU Max controllable indoor units : 16
Simple Remote
Controller (with
master control)
F
UT Y-RSRY
UT Y-RSKU
Max controllable indoor units : 16
Simple Remote
Controller
(without master
control)
F
UT Y-RHRY
UT Y-RHKU
Max controllable indoor units : 16
Wireless
Remote
Controller
UTY-LNHU
*1 Note: Di󰀨erent VRF series may be connected for each of the 4 VRF networks supported by the
unit, but di󰀨erent series may not coexist within the same network.
(VR-II Series and V-II Series can exist together on same network.)
*2 Note : For one VRF network system, total number of Touch Panel Controller, Central Remote
Controller, Network Convertor for Group Remote Controller, Modbus
®
Convertor for VRF,
BACnet
®
Gateway (Hardware) is 16, including one Network Convertor for L