Example 25 (OK)
Capacity ratio
100%
Outdoor unit
Header
Cooling
only type
Indoor unit 1
RB unit 1
RB unit 2
RB unit 3
Indoor unit 2 Indoor unit 3 Indoor unit 4
Model
Cooling
capacity
(Btu/h)
Total
capacity
(Btu/h)
Connectable indoor unit
capacity
Judgement
Min. Max.
Outdoor unit AOUA72T 72000 72000
50%
36000
150%
108000

36000 < 72000 < 108000 → OK
Capacity ratio of Cooling only type is
18000/72000=25% < 50%→ OK
Indoor unit 1 AUUA18 18000
72000
Indoor unit 2 AUUA18 18000
Indoor unit 3 AUUA18 18000
Indoor unit 4 AUUA18 18000
RB unit 1 RU01AH -
18000
7500
27000

7500 < 18000 < 27000 → OK
RB unit 2 RU01AH -
18000
7500
27000

7500 < 18000 < 27000 → OK
RB unit 3 RU01AH -
18000
7500
27000

7500 < 18000 < 27000 → OK
- (06 - 25) -